| Plan Review Notes For Permit 16040915 |
| Permit Number |
16040915 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-11-01 14:10:49 | TUESDAY, NOVEMBER 01, 2016 | | | | | | 16040915 | | | 354 MARLBOROUGH ST. | | | SF REMODEL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. ALSO NOTE THAT THE PREVIOUS | | | ELECTRICAL COMMENTS FROM 4/27/2016 STILL NEED TO BE | | | ADDRESSED WITHIN THE GENERAL NOTES. | | | | | | PROVIDE THE LOCATION OF THE ELECTRIC SERVICE, MAIN | | | DISCONNECT AND PANEL BOARD. NEC 230.70, FBC R E3601.6.2 | | | | | | VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC | | | 406.2; FBC R E4002.14 | | | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. NEC 250.94; FBC R E3609 | | | | | | SHOW THE LOCATION OF THE WATER HEATER AND DISCONNECT. | | | THE WATER HEATER REQUIRES A DISCONNECT LOCATED WITHIN | | | SIGHT OF THE WATER HEATER OR A LOCKABLE DISCONNECT. NEC | | | 422.30 FBC R E4101.5 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-373-3701 | | | | | | |
|