| 2016-11-03 14:34:28 | RESIDENTIAL (R3) FRONT BUILDING REVISION, SECOND |
| | BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | ENGINEER MAY BE CHARGED A FOUR TIMES THE PLAN REVIEW |
| | FEE IF PLANS ARE DENIED 3 TIMES OR MORE. SEE FLORIDA |
| | STATUTE 553.80(2)(B). |
| | |
| | 1- THE NEW A/C CLOSET ON THE SECOND FLOOR IS REDUCING |
| | THE WIDTH OF THE STAIRS. THIS IS NOT ALLOWED. SEC. |
| | 701.2 FBC-EXISTING BUILDING, 5TH EDITION (2014). REVISE |
| | AS REQUIRED. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 2- SCOPE OF WORK IS NOT CLEAR. PROVIDE WALL LEGEND AND |
| | CLEARLY IDENTIFY ON PLANS WHICH ARE THE EXISTING WALLS |
| | TO BE DEMOLISHED, WHICH WALLS ARE EXISTING TO REMAIN |
| | AND WHICH WALLS ARE NEW. SEC. 107.2.1 CITY AMENDMENTS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 3- NEW A/C CLOSET ON THE SECOND FLOOR ABOVE THE |
| | STAIRWAY. PROVIDE DETAIL/SPECS SHOWING COMPLIANCE WITH |
| | THE STAIRWAY HEADROOM SEC. R311.7.2 FBC-RESIDENTIAL, |
| | 5TH EDITION (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 4- A) REVISE DOOR AND WINDOW SCHEDULE AND FLOOR PLANS. |
| | ALL WINDOWS AND DOORS SHOWN ON PLANS ARE DENOMINATED AS |
| | "A". THIS IS INCORRECT. COORDINATE INFORMATION SHOWN ON |
| | PLANS WITH DOOR AND WINDOW SCHEDULE. CLARIFY SIZE OF |
| | EXTERIOR DOORS. SEC. 107.2.1 CITY AMENDMENTS. AND, |
| | CLEARLY IDENTIFY WHICH DOORS AND WINDOWS ARE GOING TO |
| | BE REPLACED. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B) CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS |
| | (SPECIALLY BEDROOM WINDOWS) AND SIZE AND TYPE OF |
| | PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH THE BEDROOM |
| | EGRESS REQUIREMENTS OF SEC. 704 OF FBC-EXISTING |
| | BUILDING, 5TH EDITION (2014). |
| | NOTE: DOOR AND WINDOW SCHEDULE SPECIFIES WINDOW TYPE |
| | "A" AS "(2)SH 24SH". 2 WINDOWS OF THIS SIZE DON'T FIT |
| | ON THE OPENINGS SHOWN ON PLANS. REVISE AS REQUIRED. |
| | ALSO, KEEP IN MIND THAT 24 SINGLE HUNG WINDOWS DON'T |
| | COMPLY WITH EGRESS, SPECIALLY FOR THE SECOND FLOOR. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 5-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) EXTERIOR DOORS AS SHOWN ON PLANS. |
| | RESPONSE: |
| | DRAWINGS SUBMITTED WITH FLORIDA PRODUCT APPROVAL |
| | FL14569 DON'T MEET THE DESIGN PRESSURES CALCULATED BY |
| | THE ENGINEER OF RECORD. NEED TO PROVIDE PRODUCT |
| | APPROVAL FOR DOORS THAT MEET THE CALCULATED DESIGN |
| | PRESSURES. SEE ENGINEER DRAWING A1 OF 4. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 7- SHEET A1: CLARIFY WHAT'S FEBC CLASS OF WORK?, |
| | ALTERATION LEVEL 11? SPECIFIED ON THE SPECIAL NOTES. |
| | NOTE: ACCORDING TO SEC. 505 FBC-EXISTING BUILDING, THIS |
| | IS ALT. LEVEL 3. REVISE INFORMATION ON PLANS AS |
| | REQUIRED. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | |
| | ****ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD |
| | SHEET. DON'T STAPLE OLD DRAWINGS TO NEW SET. SUBMITT |
| | OLD DRAWINGS FOR REFERENCE. |
| | |