Plan Review Notes
Plan Review Notes For Permit 16040915
Permit Number 16040915
Review Stop B
Sequence Number 2
Notes
Date Text
2016-11-03 14:34:28RESIDENTIAL (R3) FRONT BUILDING REVISION, SECOND
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER MAY BE CHARGED A FOUR TIMES THE PLAN REVIEW
 FEE IF PLANS ARE DENIED 3 TIMES OR MORE. SEE FLORIDA
 STATUTE 553.80(2)(B).
  
 1- THE NEW A/C CLOSET ON THE SECOND FLOOR IS REDUCING
 THE WIDTH OF THE STAIRS. THIS IS NOT ALLOWED. SEC.
 701.2 FBC-EXISTING BUILDING, 5TH EDITION (2014). REVISE
 AS REQUIRED.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- SCOPE OF WORK IS NOT CLEAR. PROVIDE WALL LEGEND AND
 CLEARLY IDENTIFY ON PLANS WHICH ARE THE EXISTING WALLS
 TO BE DEMOLISHED, WHICH WALLS ARE EXISTING TO REMAIN
 AND WHICH WALLS ARE NEW. SEC. 107.2.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- NEW A/C CLOSET ON THE SECOND FLOOR ABOVE THE
 STAIRWAY. PROVIDE DETAIL/SPECS SHOWING COMPLIANCE WITH
 THE STAIRWAY HEADROOM SEC. R311.7.2 FBC-RESIDENTIAL,
 5TH EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 4- A) REVISE DOOR AND WINDOW SCHEDULE AND FLOOR PLANS.
 ALL WINDOWS AND DOORS SHOWN ON PLANS ARE DENOMINATED AS
 "A". THIS IS INCORRECT. COORDINATE INFORMATION SHOWN ON
 PLANS WITH DOOR AND WINDOW SCHEDULE. CLARIFY SIZE OF
 EXTERIOR DOORS. SEC. 107.2.1 CITY AMENDMENTS. AND,
 CLEARLY IDENTIFY WHICH DOORS AND WINDOWS ARE GOING TO
 BE REPLACED.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 (SPECIALLY BEDROOM WINDOWS) AND SIZE AND TYPE OF
 PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH THE BEDROOM
 EGRESS REQUIREMENTS OF SEC. 704 OF FBC-EXISTING
 BUILDING, 5TH EDITION (2014).
 NOTE: DOOR AND WINDOW SCHEDULE SPECIFIES WINDOW TYPE
 "A" AS "(2)SH 24SH". 2 WINDOWS OF THIS SIZE DON'T FIT
 ON THE OPENINGS SHOWN ON PLANS. REVISE AS REQUIRED.
 ALSO, KEEP IN MIND THAT 24 SINGLE HUNG WINDOWS DON'T
 COMPLY WITH EGRESS, SPECIALLY FOR THE SECOND FLOOR.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS.
 RESPONSE:
 DRAWINGS SUBMITTED WITH FLORIDA PRODUCT APPROVAL
 FL14569 DON'T MEET THE DESIGN PRESSURES CALCULATED BY
 THE ENGINEER OF RECORD. NEED TO PROVIDE PRODUCT
 APPROVAL FOR DOORS THAT MEET THE CALCULATED DESIGN
 PRESSURES. SEE ENGINEER DRAWING A1 OF 4.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7- SHEET A1: CLARIFY WHAT'S FEBC CLASS OF WORK?,
 ALTERATION LEVEL 11? SPECIFIED ON THE SPECIAL NOTES.
 NOTE: ACCORDING TO SEC. 505 FBC-EXISTING BUILDING, THIS
 IS ALT. LEVEL 3. REVISE INFORMATION ON PLANS AS
 REQUIRED.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 ****ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD
 SHEET. DON'T STAPLE OLD DRAWINGS TO NEW SET. SUBMITT
 OLD DRAWINGS FOR REFERENCE.
  