Plan Review Notes
Plan Review Notes For Permit 16040915
Permit Number 16040915
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-27 16:44:03FAILED 2ND ELECTRICAL REVIEW
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 CORRECTIONS REQUIRED:
 1. YOUR GENERAL NOTES SECTION ON NOTE 7 INDICATES THAT
 ALL CONDUCTORS SHALL BE THHN. PLEASE NOTE THAT IT IS
 NOT CONDUCTOR GAUGE BUT THE AMBIENT CONDITIONS WHICH
 DETERMINE CONDUCTOR INSULATION, HENCE: WET OR DRY
 LOCATIONS.
 2. NEC 404.2(C). WHERE SWITCHES CONTROLLING LIGHTING
 LOADS SUPPLIED BY A GROUNDED BRANCH CIRCUIT, THE
 GROUNDED BRANCH CIRCUIT CONDUCTOR FOR THE CONTROLLED
 LIGHTING CIRCUIT SHALL BE PROVIDED AT THE SWITCH.
 3. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 4. NEC 406.12 TAMPER-RESISTANT RECEPTACLES IN DWELLING
 UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT,
 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER
 RESISTANT RECEPTACLES.
 5. IDENTIFY THE LOCATION OF THE ELECTRIC WATER HEATER
 ON THE PLANS.
 6. NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT.
 OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. THIS
 REFERS PRIMARILY TO THE AREA BELOW THE FIRST FLOOR
 STAIRS OR ALONG THAT SAME WALL.
 7. NEC 210.52(H). IN DWELLING UNITS, HALLWAYS OF 10 FT
 OR MORE IN LENGTH SHALL HAVE AT LEAST ONE RECEPTACLE
 OUTLET.
 8. NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 9. FBC-R402.4.4. RECESSED LIGHTING INSTALLED IN THE
 BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND BE
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED &
 UNCONDITIONED SPACES.
 10. FBC-R404.1 A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER