| 2016-04-27 16:44:03 | FAILED 2ND ELECTRICAL REVIEW |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 |
| | EDITION |
| | |
| | CORRECTIONS REQUIRED: |
| | 1. YOUR GENERAL NOTES SECTION ON NOTE 7 INDICATES THAT |
| | ALL CONDUCTORS SHALL BE THHN. PLEASE NOTE THAT IT IS |
| | NOT CONDUCTOR GAUGE BUT THE AMBIENT CONDITIONS WHICH |
| | DETERMINE CONDUCTOR INSULATION, HENCE: WET OR DRY |
| | LOCATIONS. |
| | 2. NEC 404.2(C). WHERE SWITCHES CONTROLLING LIGHTING |
| | LOADS SUPPLIED BY A GROUNDED BRANCH CIRCUIT, THE |
| | GROUNDED BRANCH CIRCUIT CONDUCTOR FOR THE CONTROLLED |
| | LIGHTING CIRCUIT SHALL BE PROVIDED AT THE SWITCH. |
| | 3. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE |
| | SUPPORT OF CEILING FANS SHALL BE MARKED BY THE |
| | MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE |
| | THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT |
| | PADDLE FANS HEAVIER THAN 70 LBS. |
| | 4. NEC 406.12 TAMPER-RESISTANT RECEPTACLES IN DWELLING |
| | UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT, |
| | 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER |
| | RESISTANT RECEPTACLES. |
| | 5. IDENTIFY THE LOCATION OF THE ELECTRIC WATER HEATER |
| | ON THE PLANS. |
| | 6. NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT. |
| | OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. THIS |
| | REFERS PRIMARILY TO THE AREA BELOW THE FIRST FLOOR |
| | STAIRS OR ALONG THAT SAME WALL. |
| | 7. NEC 210.52(H). IN DWELLING UNITS, HALLWAYS OF 10 FT |
| | OR MORE IN LENGTH SHALL HAVE AT LEAST ONE RECEPTACLE |
| | OUTLET. |
| | 8. NEC 250.94 BONDING FOR OTHER SYSTEMS. THE |
| | INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| | INSTALLED. |
| | 9. FBC-R402.4.4. RECESSED LIGHTING INSTALLED IN THE |
| | BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND BE |
| | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED & |
| | UNCONDITIONED SPACES. |
| | 10. FBC-R404.1 A MINIMUM OF 75% OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICIENCY LAMPS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |