2016-04-21 18:43:22JOB PERMIT NUMBER: 16040854
 JOB ADDRESS: 1200 S FLAGLER DRIVE
 WEST PALM BEACH FLORIDA
 DATE: APRIL 21 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 - FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 - NEC 406.11 TAMPER-RESISTANT RECEPTACLES IN DWELLING
 UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL 125-VOLT,
 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED TAMPER
 RESISTANT RECEPTACLES.
 - NEC 404.2C SWITCHES CONTROLLING LIGHTING LOADS
 SUPPLIED BY A GROUNDED GENERAL PURPOSE BRANCH CIRCUIT,
 THE GROUNDED CIRCUIT CONDUCTOR FOR THE CONTROLLED
 LIGHTING CIRCUIT SHALL BE PROVIDED AT THE SWITCH
 LOCATION.
 - NEC 210.52(E)(3) BALCONIES GREATER THAN 20 SQ. FT.
 SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET INSTALLED
 WITHIN THE PERIMETER OF THE BALCONY.
 - MISSING SMOKE DETECTORS IN NEW LIVING ROOM , NEW
 DINING ROOM , NEW DEN , NEW OFFICE , ALL ALARMS MUST BE
 INTERCONNECTED PER RESIDENTIAL CODE SECTIONS 314 & 315
 PLUS NFPA 72 CHAPTER 29.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  