2017-03-08 13:01:15****CORRECTIONS****
 COURTESY REVIEW BASED ON PHOTOGRAPHS SENT VIA EMAIL
 FROM CONTRACTOR
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FLORIDA BUILDING CODE, BUILDING 5TH EDITION (2014)
 SECTION 1609:
  
 COMMENT FROM PREVIOUS BUILDING REVIEW #4 DATED
 3/6/2017:
  
 THE GATE DETAIL WAS PROVIDED. THE PLAN STATES THAT
 DESIGN CRITERIA IS FOR "80% OPEN SIGN". CALCULATIONS
 ARE FOR 20% SOLID SURFACE.
  
 THE GATE DETAIL GRAPHICALLY APPEARS TO DEPICT A SOLID
 GATE. A NOTE STATES THAT THE LOUVERS HAVE A .5"
 OVERLAP. IT IS NOT CLEAR HOW THE GATE MEETS THE
 CRITERIA OF 80% OPEN.
  
 REVISE PLAN TO CLARIFY GATE DESIGN (NEEDS TO BE 80%
 OPEN) OR GATE DESIGN CRITERIA (CURRENTLY APPEARS
 TO REQUIRE THAT THE GATE IS 80% OPEN, BUT PLAN SHOWS A
 SOLID GATE).
  
 COURTESY REVIEW 3/8/17; PHOTOGRAPHS OF PROPOSED GATE
 SENT VIA EMAIL BY CONTRACTOR:
  
 BASED ON THE PHOTOGRAPHS PROVIDED, THE PROPOSED GATE IS
 NOT MEET THE 80% OPEN CRITERIA (REQUIREMENT BASED
 ON THE GATE FOUNDATION ABILITY TO WITHSTAND WIND LOADS)
 UNLESS THE WIND IS PARALLEL TO THE GATE. IF THE
 WIND IS PERPENDICULAR TO THE GATE, THE WIND EFFECT WILL
 BE SIMILAR TO THE EFFECT ON A SOLID SURFACE.
  
 THIS ISSUE HAS BEEN DISCUSSED WITH THE BUILDING
 OFFICIAL. IF THE ENGINEER OF RECORD DISAGREES, PLEASE
 HAVE
 HIM CALL ROBERT BROWN, 561-805-6652 OR EMAIL RATIONALE
 FOR THIS DESIGN MEETING HIS REQUIREMENT OF 80% OPEN
 TO [email protected] (AND PLEASE CC [email protected]).
  
 THE ENGINEERED DETAIL IS NOT CLEAR AS TO CONSTRUCTION,
 FBC 107. THE BUILDING OFFICIAL IS ALSO IN AGREEMENT
 THAT A SECTION IS REQUIRED TO SHOW THE ANGLE OF THE
 GATE LOUVERS; THE DRAWINGS PROVIDED DO NOT ACCURATELY
 DEPICT PROPOSED CONSTRUCTION. THE SECTION SHOULD
 PROVIDE ENOUGH DIMENSIONS TO CLEARLY DEPICT PROPOSED
 CONSTRUCTION.
  
 PLEASE ALSO REVISE REFERENCE TO "SIGN" DESIGN CRITERIA
 (APPEARS THAT THIS SHOULD REFERENCE "GATE") OR CLARIFY
  
 TO CLARIFY THE SEQUENCE OF SUBMITTALS AND PLAN REVIEWS:
  
 1/9/2017 REVIEW, A GATE DETAIL PREPARED BY SIVANANTHAN
 SRITHARAN, PE ON 2/09/2016 INCLUDES A DETAIL (2-S2)
 WHICH
 CLARIFIES THE PROPOSED DESIGN BUT LACKS INFORMATION
 REGARDING THE PERCENTAGE OF OPEN AREA.
 2/10/2017 REVIEW, THIS GATE DETAIL WAS VOIDED BY
 APPLICANT AND A REPLACEMENT DETAIL NOT PROVIDED.
 3/6/2017 REVIEW, A NEW DETAIL PREPARED BY EVAN KENNEDY,
 PE ON 1/27/2017 WAS SUBMITTED FOR REVIEW.
  
  
  
  