| Plan Review Notes For Permit 16040833 |
| Permit Number |
16040833 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-02-10 09:47:21 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | SEE PREVIOUS LIST FOR COMMENTS TO BE ADDRESSED. | | | | | | THE RESUBMITTAL DOES NOT INCLUDE GATE ENGINEERING. ONE | | | OLD SET OF PLANS WAS PROVIDED, AND THE GATE DETAIL IS | | | MARKED "VOID". | | | | | | FBC 107, PROVIDE GATE ENGINEERING SO THE REVIEW CAN BE | | | COMPLETE. NOTE THAT THE FIRST COMMENT LIST STATES THAT | | | 25% SOLID WAS A LIMITATION, BUT NEW PLAN SPECS 80% OPEN | | | (SO ONLY 20% SOLID ALLOWED). THE NEW DETAIL IS TO SHOW | | | COMPLIANCE. | | | | | | |
|