| Plan Review Notes For Permit 16040833 |
| Permit Number |
16040833 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-05 16:58:34 | 2ND REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] IN ADDITION TO THE MANUFACTURE SPECS PROVIDE AN | | | ELECTRICAL DETAIL SHOWING CONDUIT & WIRE SIZE, CIRCUIT | | | # & AMPERAGE OF THE BRANCH CIRCUIT FEEDING THE GATE | | | SWING MOTORS. FBC 107 (2ND REQUEST). |
|