| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - SHOWS OVERHEAD AND UNDERGROUND SERVICE CONDUCTORS ? |
| | NEC ONLY ALLOWS ONE SERVICE PER BUILDING IN ACCORDANCE |
| | TO ARTICLE 230.2. IF THE INTENT IS TO METER THE GARAGE |
| | SEPARATE FROM THE 2ND FLOOR WHY DOES EACH DISCONNECT |
| | SHOW A RISER ? ELECTRICAL SUB ? PANEL LOCATIONS MUST BE |
| | SHOWN ON FLOOR PLANS UNLESS THE 100 AMP MAIN BREAKER |
| | INCLUDES THE BRANCH CIRCUITS TO THEIR PROSPECTIVE |
| | LOADS. PLEASE CLARIFY SERVICE RISER DIAGRAM LAYOUT? |
| | - PROVIDE LOAD CALCULATIONS AND A PANEL SCHEDULE |
| | INDICATING WIRE AND BREAKER SIZES. WPBA 107 |
| | - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE |
| | INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| | INSTALLED. |
| | - FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN |
| | 10 FEET OF EACH SLEEPING ROOM. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |