| 2016-05-09 17:15:48 | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED |
| | |
| | FLORIDA ENERGY CODE - SECTION R202 RENOVATED BUILDINGS |
| | - A RESIDENTIAL OR NONRESIDENTIAL BUILDING UNDERGOING |
| | ALTERATION THAT VARIES INSULATION, HVAC SYSTEMS, WATER |
| | HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS, |
| | PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30 |
| | PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE. |
| | |
| | R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED |
| | IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES |
| | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR |
| | FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT |
| | EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT |
| | INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL |
| | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM |
| | EXHAUST SYSTEMS. |
| | |
| | PROVIDE ENERGY AND HEAT LOAD CALCULATIONS. |
| | |
| | PROVIDE AHRI. |
| | |
| | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | PROVIDE CONDENSER TIE DOWN SCHEDULE. |
| | |