| Date |
Text |
| 2016-08-18 17:04:04 | BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE |
| | INFORMATION PRIOR TO INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS): |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| | A) ARCHED ENTRY DOOR (USE OF EXISTING HISTORIC ENTRY |
| | DOOR WAS APPROVED BY ROBERT BROWN (BUILDING OFFICIAL). |
| | THE DOOR STILL NEEDS TO COMPLY WITH THE PRODUCT |
| | APPROVAL REQUIREMENT. PROVIDE LOCAL PRODUCT APPROVAL |
| | APPLICATION AND COMPLETE ENGINEERING PACKAGE (2 COPIES) |
| | FOR BUILDING OFFICIAL APPROVAL. |
| | B) FLAT ROOF WITH APPROVED ASSEMBLY AS SPECIFIED ON |
| | PLANS. |
| | C) PRECAST LINTELS AS SHOWN ON PLANS. |
| | D) ROOF TILE ADHESIVE. SEE ROOF TILE NOA FOR LISTED |
| | ADHESIVES. |
| | 2- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS. |
| | 3- NEW GEOTECHNICAL REPORT SUBMITTED (2 COPIES) TO HAVE |
| | THE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED |
| | BY CHAPTER 471 FLORIDA STATUTE. |
| | |
| | IMPORTANT: |
| | (1) ELEVATION CERTIFICATES WILL BE REQUIRED DURING |
| | CONSTRUCTION. PLEASE COORDINATE WITH SAMANTHA HILL AT |
| | (561)805-6724 AND [email protected] TO AVOID CONFLICTS OR |
| | DELAYS. |
| | (2) SPECIAL INSPECTOR IS REQUIRED FOR THE CONSTRUCTION |
| | OF AUGER CAST PILES. PLEASE COORDINATE WITH KEN CONRAD |
| | (CHIEF BUILDING INSPECTOR) AT (561)805-6666 AND |
| | [email protected] FOR APPROVAL OF SPECIAL INSPECTOR TO |
| | AVOID CONFLICTS OR DELAYS. |
| | (3) PROVIDE PILES SHOP DRAWINGS APPROVED BY THE |
| | STRUCTURAL ENGINEER OF RECORD. |
| | (4) SPECIAL INSPECTOR IS REQUIRED FOR THE CONCRETE |
| | CONSTRUCTION AS REQUIRED BY SEC. 110.3.9 CITY |
| | AMENDMENTS. (CONCRETE STRENGTH DESIGN IS MORE THAN 3000 |
| | PSI). PLEASE COORDINATE WITH KEN CONRAD (CHIEF BUILDING |
| | INSPECTOR) AT (561)805-6666 AND [email protected] FOR |
| | APPROVAL OF SPECIAL INSPECTOR TO AVOID CONFLICTS OR |
| | DELAYS. |
| | |
| | |