| Plan Review Notes For Permit 16040779 |
| Permit Number |
16040779 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-29 14:39:42 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR: | | | | | | A) FLAT ROOF NOA 13-1217.01 SUBMITTED: | | | (1) SELECTED ASSEMBLY ON PAGE 30 OF 33 IS FOR AN | | | NON-INSULATED ROOF SYSTEM. ARCHITECTURAL PLANS CALL FOR | | | R-21 MIN. RIGID INSULATION (SEE KEY NOTE #0703 ON | | | ARCHITECTURAL PLANS). NEED TO SELECT ASSEMBLY WITH | | | RIGID INSULATION AS SPECIFIED BY THE ARCHITECT. NOTE: | | | IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED BY GENERAL LIMITATION | | | #7. ASSEMBLIES WITH GENERAL LIMITATION #9 DON'T ALLOW | | | RAS 117 CALCULATIONS. | | | | | | B) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF | | | RECORD. (NOTE: DESIGNER OF RECORD NEEDS TO SPECIFY ROOF | | | TILE FASTENING). | | | RESPONSE: | | | (1) NOA 12-0529.01 SUBMITTED EXPIRED ON 01/03/16. NEED | | | CURRENT NOA. | | | (2) ROOF TILE ADHESIVE RTA-1 IS NOT LISTED ON THE ROOF | | | TILE NOA SUBMITTED. THIS ADHESIVE NEEDS TO BE LISTED ON | | | THE ROOF TILE OR COMPLETE PROVIDE COMPLETE PRODUCT | | | APPROVAL INFORMATION AND APPLY FOR LOCAL PRODUCT | | | APPROVAL FOR PROPOSED INSTALLATION. LOCAL PRODUCT | | | APPROVAL TO BE APPROVED BY THE BUILDING OFFICIAL. |
|