| Date |
Text |
| 2016-07-27 14:31:15 | NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING |
| | REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014) |
| | |
| | ****NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH "PROVISO" ONCE THE |
| | ENERGY CALCULATIONS COMMENTS ARE ADDRESSED. PERMIT MAY |
| | BE ISSUED AND REQUIRED INFORMATION MAY BE SUBMITTED |
| | LATER PRIOR TO INSPECTIONS TO AVOID CONFLICTS OR |
| | DELAYS. FEES MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO |
| | OPTION IS REQUESTED AT THIS TIME OR IF RE-SUBMITTING |
| | REQUIRED INFORMATION BEFORE ISSUING THE PERMIT. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | FOR IMPACT FESS ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | RESPONSE: |
| | PLANS SUBMITED HAVE THE PBC STAMP (MU-2016-16556). BUT |
| | SUBMITTAL IS MISSING THE COPY OF THE PAID RECEIPT. |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED: |
| | A) OWNER/AGENT TO CERTIFY AND DATE THE ENERGY |
| | CALCULATIONS AT THE BOTTOM OF THE FORM AS REQUIRED BY |
| | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). NOTE: BOTH FORMS MAIN HOUSE AND |
| | GARAGE/APARTMENT. |
| | |
| | B) CONTRACTOR TO COMPLETE THE EPL DISPLAY CARD AS |
| | REQUIRED BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). NOTE: BOTH FORMS MAIN HOUSE AND |
| | GARAGE/APARTMENT. |
| | |
| | C) COMPLETE THE INSPECTION COMPONENT CRITERIA TABLE |
| | 402.4.1.1 SUBMITTED. SEC. R405.4.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). NOTE: BOTH FORMS MAIN |
| | HOUSE AND GARAGE/APARTMENT. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | ORIGINAL COMMENT: |
| | A) ARCHED ENTRY DOOR AS SHOWN ON PLANS. |
| | RESPONSE: |
| | USE OF EXISTING HISTORIC ENTRY DOOR WAS APPROVED BY |
| | ROBERT BROWN (BUILDING OFFICIAL). THE DOOR STILL NEEDS |
| | TO COMPLY WITH THE PRODUCT APPROVAL REQUIREMENT. THIS |
| | MAY BE ACCOMPLISHED BY APPLYING FOR ONE TIME LOCAL |
| | PRODUCT APPROVAL. PROVIDE COMPLETE ENGINEERING ANALYSIS |
| | FOR LOCAL PRODUCT APPROVAL TO BE REVIEWED AND APPROVED |
| | BY THE BUILDING OFFICIAL. PLEASE CONTACT ROBERT BROWN |
| | FOR SUBMITTAL PACKAGE REQUIREMENTS. NOTE: IF THERE IS |
| | GLAZING IN THE DOOR, THEN SUBMITT HURRICANE IMPACT |
| | PROTECTION INFORMATION AT TIME OF ENTRY DOOR LOCAL |
| | PRODUCT APPROVAL SUBMITTAL. |
| | |
| | B) FLAT ROOF NOA 13-1217.01 SUBMITTED: |
| | (1) SELECTED ASSEMBLY ON PAGE 30 OF 33 IS FOR AN |
| | NON-INSULATED ROOF SYSTEM. ARCHITECTURAL PLANS CALL FOR |
| | R-21 MIN. RIGID INSULATION (SEE KEY NOTE #0703 ON |
| | ARCHITECTURAL PLANS). NEED TO SELECT ASSEMBLY WITH |
| | RIGID INSULATION AS SPECIFIED BY THE ARCHITECT. NOTE: |
| | IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED BY GENERAL LIMITATION |
| | #7. ASSEMBLIES WITH GENERAL LIMITATION #9 DON'T ALLOW |
| | RAS 117 CALCULATIONS. |
| | |
| | ORIGINAL COMMENT: |
| | C) PRECAST LINTELS AS SHOWN ON PLANS. |
| | RESPONSE: |
| | NOT SUBMITTED. |
| | |
| | ORIGINAL COMMENT: |
| | D) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF |
| | RECORD. (NOTE: DESIGNER OF RECORD NEEDS TO SPECIFY ROOF |
| | TILE FASTENING. SEE ITEM # 5 BELOW). |
| | RESPONSE: |
| | (1) NOA 12-0529.01 SUBMITTED EXPIRED ON 01/03/16. NEED |
| | CURRENT NOA. |
| | (2) ROOF TILE ADHESIVE RTA-1 IS NOT LISTED ON THE ROOF |
| | TILE NOA SUBMITTED. THIS ADHESIVE NEEDS TO BE LISTED ON |
| | THE ROOF TILE OR COMPLETE PROVIDE COMPLETE PRODUCT |
| | APPROVAL INFORMATION AND APPLY FOR LOCAL PRODUCT |
| | APPROVAL FOR PROPOSED INSTALLATION. LOCAL PRODUCT |
| | APPROVAL TO BE APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | ORIGINAL COMMENT: |
| | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO VERIFY |
| | COMPLIANCE WITH THE COMPONENTS AND CLADDING DESIGN |
| | PRESSURES. |
| | RESPONSE: |
| | THE STRUCTURAL ENGINEER OF RECORD IS THE ONE THAT NEEDS |
| | TO APPROVE THE PRODUCT APPROVALS. PRODUCT APPROVALS ARE |
| | FOR COMPONENTS AND CLADDING. THAT'S WHY THE STRUCTURAL |
| | ENGINEER NEEDS TO APPROVE THEM. NOTE: ENGINEER TO |
| | PROVIDE REVIEW STAMP ON EACH PRODUCT APPROVAL OR TO |
| | PROVIDE LETTER THAT CLEARLY IDENTIFY EACH PRODUCT |
| | APPROVAL (NOA OR FLORIDA PRODUCT APPROVAL NUMBER, |
| | MODEL, ETC,) REVIEW LETTER SUBMITTED BY THE ARCHITECT |
| | IS NOT ACCEPTABLE BECAUSE IS TOO GENERAL. THERE IS NO |
| | WAY OF REFERENCING WHICH SPECIFIC PRODUCT APPROVALS |
| | WERE APPROVED. |
| | |
| | ORIGINAL COMMENT: |
| | 5- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| | SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF |
| | SCREWS. IF SPECIFYING ADHESIVE, THEN ADHESIVE PRODUCT |
| | APPROVAL IS REQUIRED. (NOTE: DESIGNER OF RECORD TO |
| | SPECIFY THE MINIMUM ATTACHMENT RESISTANCE REQUIRED FOR |
| | THIS BUILDING. SEE NOA 14-0605.03 SUBMITTED FOR |
| | REFERENCE). |
| | RESPONSE: |
| | DESIGNER OF RECORD IS REQUIRED TO SPECIFY SPECIFIC |
| | FASTENING OPTION. THE PRODUCT APPROVAL IS TO VERIFY |
| | THAT IT MEETS THE DESIGNER OF RECORD SPECIFICATIONS. |
| | RESPONSE LETTER STATING "SEE ATTACHED NOA" DOESN'T |
| | ADDRESS THIS REQUIREMENT. |
| | |
| | 6- NEW GEOTECHNICAL REPORT SUBMITTED (2 COPIES) NEEDS |
| | TO HAVE THE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| | |
| | |
| | IMPORTANT FOR YOUR INFORMATION: |
| | (1) ELEVATION CERTIFICATES WILL BE REQUIRED DURING |
| | CONSTRUCTION. PLEASE COORDINATE WITH SAMANTHA HILL AT |
| | (561)805-6724 AND [email protected] TO AVOID CONFLICTS OR |
| | DELAYS. |
| | |
| | (2) SPECIAL INSPECTOR IS REQUIRED FOR THE CONSTRUCTION |
| | OF AUGER CAST PILES. PLEASE COORDINATE WITH KEN CONRAD |
| | (CHIEF BUILDING INSPECTOR) AT (561)805-6666 AND |
| | [email protected] FOR APPROVAL OF SPECIAL INSPECTOR TO |
| | AVOID CONFLICTS OR DELAYS. |
| | |
| | (3) PROVIDE PILES SHOP DRAWINGS APPROVED BY THE |
| | STRUCTURAL ENGINEER OF RECORD. |
| | |
| | (4) PLEASE CONTACT/COORDINATE ALL ELEVATIONS |
| | CERTIFICATES WITH SAMANTHA HILL TO AVOID CONFLICTS OR |
| | DELAYS AFTER PERMIT IS ISSUED. |
| | SAMANTHA HILL |
| | PHONE: 805-6724 EXT: 6724 |
| | E-MAIL: [email protected] |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | FROM: [email protected] [[email protected]] |
| | SENT: THURSDAY, JUNE 30, 2016 8:12 PM |
| | TO: MARTHA BURITICA |
| | CC: [email protected]; [email protected]; RICK GONZALEZ; |
| | [email protected] |
| | SUBJECT: RE: 15040_GREEN RESIDENCE HISTORIC |
| | RECONSTRUCTION - PERMIT #16040779 |
| | |
| | MARTHA, |
| | I HAVE DISCUSSED THE USE OF THE EXISTING DOOR WITH BOTH |
| | RICK GONZALEZ AND JULIO GOMEZ. I EXPECT THAT YOU GOT |
| | FEEDBACK FROM THEM. IN CASE YOU DID NOT, PLEASE NOTE |
| | THAT I TOLD THEM THAT USING THE ORIGINAL DOOR IS OK |
| | PROVIDED THERE IS AT LEAST ONE OTHER SWING DOOR THAT |
| | CAN BE USED TO EXIT THE PROPERTY, WITHOUT GOING THROUGH |
| | A GARAGE. OF COURSE, THAT DOOR MUST MEET THE MINIMUM |
| | WIDTH REQUIREMENT. |
| | REGARDS |
| | |
| | ROBERT BROWN, CBO |
| | BUILDING OFFICIAL / BUILDING DIVISION MANAGER |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES DEPARTMENT ? BUILDING DIVISION |
| | (561) 805 6652 |
| | |