| Plan Review Notes For Permit 16040767 |
| Permit Number |
16040767 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-18 14:55:18 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1-THE DESIGN PRESSURES FOR THE SINGLE HUNG WINDOW SHOWN | | | ON FLORIDA PRODUCT APPROVAL FL17499 SUBMITTED DON'T | | | MEET THE DESIGN PRESSURES THAT WERE CALCULATED BY THE | | | ENGINEER OF RECORD. PROVIDE PRODUCT APPROVAL THAT MEETS | | | THE CALCULATED DESIGN PRESSURES REQUIRED BY SEC. R301 | | | OF FBC-RESIDENTIAL, 5TH EDITION, (2014). | | | | | | 2- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT APPROVAL | | | BEFORE SUBMITTAL AS REQUIRED BY SEC. 107.3.4.1 CITY | | | AMENDMENTS | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|