| 2016-09-08 10:32:37 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | THESE PROVISO COMMENTS ARE POSTED IN AN EFFORT TO MOVE |
| | THIS PROJECT FORWARD. |
| | |
| | THESE DEFICIENCIES ARE NOTED ON THE 12TH FL WHICH MAY |
| | ALLOW AMPLE TIME FOR CONTINUED REVIEW, INFORMATION |
| | SHARING AND IF APPLICABLE, SUBMITTED REVISIONS WHILE |
| | CONSTRUCTION BEGINS. |
| | |
| | |
| | PREVIOUS COMMENTS: |
| | |
| | 4) SHEET AS 212A - INDICATES A 48" DOOR IN THE |
| | NORTHWEST CORNER WITH AN EXIT CAPACITY OF 300. |
| | |
| | PER NFPA 101, CHAPTER 7, INDICATES THE CAPACITY OF OF |
| | 48" DOOR AS 240 MAXIMUM. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | NEW COMMENT: |
| | |
| | THERE ARE TWO LIFE SAFETY PLAN SHEETS FOR THE AMENITY |
| | DECK SHEET AS212 & AS 212A. SHEET AS212A SHOWS A HIGHER |
| | OCCUPANCY LOAD. ONCE AGAIN WHICH IS THE ACCURATE |
| | OCCUPANCY LOAD? IN YOUR RESPONSE YOU CITED AN EXCEPTION |
| | FROM |
| | THEFBC FOR SHEET AS212A TO ALLOW MORE THROUGH A 48" |
| | OPENING. THE FFPC DOES NOT HAVE THAT EXCEPTION. SHOULD |
| | AS212A BE THE OCCUPANCY LOAD SHEET BEING THE HIGHER |
| | LOAD COUNT THE 48" EXIT IS NON COMPLIANT PER THE FFPC, |
| | THE |
| | STRICTER REQUIREMENT. |
| | |
| | PLEASE REVIEW AND CORRECT |
| | |
| | |
| | 5) SHEET 212A - INDICATES AN 60" WIDE STAIR IN THE |
| | NORTHWEST CORNER WITH AN EXIT CAPACITY OF 300. |
| | |
| | PER NFPA 101, CHAPTER 7, INDICATES THE CAPACITY OF OF |
| | 60" STAIR AS 200 MAXIMUM. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | NEW COMMENT: |
| | |
| | THERE ARE TWO LIFE SAFETY PLAN SHEETS FOR THE AMENITY |
| | DECK SHEET AS212 & AS 212A. SHEET AS212A SHOWS A HIGHER |
| | OCCUPANCY LOAD. ONCE AGAIN WHICH IS THE ACCURATE |
| | OCCUPANCY LOAD? IN YOUR RESPONSE YOU CITED AN EXCEPTION |
| | FROM |
| | THEFBC FOR SHEET AS212A TO ALLOW MORE THROUGH A 60" |
| | STAIR OPENING. THE FFPC DOES NOT HAVE THAT EXCEPTION. |
| | THE HIGHEST LOAD THROUGH A STAIR GREATER THAN 44" IS |
| | 225 PER NFPA 101, CHAPTER 7, 7.3.3.2. SHOULD AS212A BE |
| | THE |
| | OCCUPANCY LOAD SHEET BEING THE HIGHER LOAD COUNT THE |
| | 60" EXIT IS NON COMPLIANT PER THE FFPC, THE STRICTER |
| | REQUIREMENT. |
| | |
| | PLEASE REVIEW AND CORRECT |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |