| 2016-08-18 14:10:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET AS 201- INDICATES A STAIR EXITING IN THE ALLEY |
| | ON THE NORTHEAST AREA; HOWEVER, IT DOES NOT SHOW WHERE |
| | THIS STAIRS COMES FROM ON ANY OTHER SHEET. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 2) SHEET AS 202 - INDICATES A STAIR (STAIR # 5?) |
| | LEADING DOWN: HOWEVER, NO OTHER SHEET SHOW WHERE IT |
| | GOES OR CONNECTS TO. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 3) SHEETS AS 212 & 212A - A POOL GATE ON THE NORTHWEST |
| | CORNER THAT IS INDICATING FOR 273 EXITING OCCUPANTS |
| | APPEARS TO TOO SMALL IN WIDTH TO ACCOMODATE. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 4) SHEET AS 212A - INDICATES A 48" DOOR IN THE |
| | NORTHWEST CORNER WITH AN EXIT CAPACITY OF 300. |
| | |
| | PER NFPA 101, CHAPTER 7, INDICATES THE CAPACITY OF OF |
| | 48" DOOR AS 240 MAXIMUM. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 5) SHEET 212A - INDICATES AN 60" WIDE STAIR IN THE |
| | NORTHWEST CORNER WITH AN EXIT CAPACITY OF 300. |
| | |
| | PER NFPA 101, CHAPTER 7, INDICATES THE CAPACITY OF OF |
| | 60" STAIR AS 200 MAXIMUM. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 5) SHEETS AS 212 & 212A - TWO EXITS ARE INDICATING ON |
| | THE NORTHEAST CORNER OF THE AMENITIES DECK THAT APEAR |
| | TO BE TOO CLOSE TOGETHER TO COMPLY WITH THE MEANS OF |
| | EGRESS CODE. |
| | |
| | NFPA 101, CHAPTER 7, MEANS OF EGRESS |
| | |
| | 7.5.1.3.6 IN OTHER THAN EXISTING BUILDINGS, WHERE MORE |
| | THAN TWO EXITS, EXIT ACCESSES, OR EXIT DISCHARGES ARE |
| | REQUIRED, AT LEAST TWO OF THE REQUIRED EXITS, EXIT |
| | ACCESSES, OR EXIT DISCHARGES SHALL BE ARRANGED TO |
| | COMPLY WITH THE MINIMUM SEPARATION DISTANCE |
| | REQUIREMENT. |
| | |
| | 7.5.1.3.7 THE BALANCE OF THE EXITS, EXIT ACCESSES, OR |
| | EXIT DISCHARGES SPECIFIED IN 7.5.1.3.6 SHALL BE LOCATED |
| | SO THAT, IF ONE BECOMES BLOCKED, THE OTHERS ARE |
| | AVAILABLE. |
| | |
| | |
| | PLEAASE REVIEW AND CORRECT. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |