Plan Review Notes
Plan Review Notes For Permit 16040741
Permit Number 16040741
Review Stop P
Sequence Number 1
Notes
Date Text
2016-07-26 17:33:151ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENT:
  
 1. SHEETS 1.02/1.06/1.11/1.12 EACH CONTROLLER IS
 REQUIRED TO HAVE A RAIN SENSOR. PER FAC
 40C-2.042(2)(A)5.
  
 2.SHT. IR 1.02 HAS A NOTE CONNECT TO POTABLE WATER
 SYSTEM FOR AGILITY FIELD IRR YOU SHALL PROVIDE A
 BACKFLOW FOR ANY CONNECTIONS TO POTABLE WATER SYSTEM.
 PER FBC PL 608.16.5 CONNECTIONS TO LAWN IRRIGATION
 SYSTEMS.
 THE POTABLE WATER SUPPLY TO LAWN IRRIGATION SYSTEMS
 SHALL BE PROTECTED AGAINST BACKFLOW BY AN ATMOSPHERIC
 VACUUM BREAKER, A PRESSURE VACUUM BREAKER ASSEMBLY OR A
 REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION
 ASSEMBLY. VALVES SHALL NOT BE INSTALLED DOWNSTREAM FROM
 AN ATMOSPHERIC VACUUM BREAKER. WHERE CHEMICALS ARE
 INTRODUCED INTO THE SYSTEM, THE POTABLE WATER SUPPLY
 SHALL BE PROTECTED AGAINST BACKFLOW BY A REDUCED
 PRESSURE PRINCIPLE BACKFLOW PREVENTION ASSEMBLY.