| Plan Review Notes For Permit 16040736 |
| Permit Number |
16040736 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-18 10:12:41 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE SHOW LIGHTING OUTLETS PER FBC RES E3903.3 | | | EGRESS OF DOORS OUTSIDE. | | | 2. SHOW THE DRYER OUTLET ON FLOOR PLAN FBC 107.3.5 | | | 3. LABEL THE LIGHTING OUTLET ABOVE SHOWER TO BE | | | RECESSED FIXTURE, VAPOR PROOF RATED. E4003.9 | | | 4. CLARIFY ELECTRICAL KEYNOTES AS SOME ARE NOT | | | APPLICABLE TO SCOPE OF WORK. DELETE N/A TO SCOPE. | | | 5. PLEASE SHOW AND ADD A WP WR RESISTANT RECEPTACLE ON | | | THE EXTERIOR OF DETACHED GARAGE. FBC E3901.7 | | | 6. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|