| Plan Review Notes For Permit 16040726 |
| Permit Number |
16040726 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-18 10:46:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SUBMITTED PLAN INDICATES A PROPOSED WATER | | | CURTAIN ON GLASS WALLS. EACH SECTION OF GLASS WALL HAS | | | DOOR THAT OPEN. A WATER CURTAIN IN THIS INSTALLTION IS | | | A MISAPPLICATION OF THE CODE AS A WATER CURTAIN CAN NOT | | | PROTECT AN OPENING. IT CAN PROTECT FIXED GLASS. | | | | | | WHAT IS THE INTENT OF THE WATER CURTAIN. IS THE WALL | | | REQUIRED TO BE RATED? | | | | | | PLEASE REVIEW WITH THE ENGINEER OF RECORD. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | |
|