Plan Review Notes
Plan Review Notes For Permit 16040708
Permit Number 16040708
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-25 15:14:25REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 PASSED WITH A PROVISO
  
 NOTICE TO ELECTRICAL CONTRACTOR
 ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY
 WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED
 STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE
 RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE
 SEALING MATERIAL.
  
 NEC 110.24 AVAILABLE FAULT CURRENT, NEC 110.16 ARC
 FLASH HAZARD
 A ? FIELD MARKING, SHALL INCLUDE DATE AND BE SUITABLE
 TO WITHSTAND ENVIRONMENT INVOLVED.
 B ? MODIFICATIONS, RECALCULATIONS NECESSARY TO ENSURE
 SUFFICIENT AT LINE TERMINALS OF EQUIPMENT.
  