| 2016-04-18 09:57:28 | JOB PERMIT NUMBER: 16040635 |
| | JOB ADDRESS: 4807 GEORGIA AVENUE |
| | WEST PALM BEACH FLORIDA |
| | DATE: APRIL 18 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - NEC 410.36 B LUMINAIRES SHALL BE SECURELY FASTENED TO |
| | THE FRAMING MEMBER BY MECHANICAL MEANS. SUSPENDED |
| | CEILING SHALL HAVE ADEQUATE STRENGTH TO ATTACH LIGHTING |
| | OR THE LUMINAIRES SHALL BE INDEPENDENTLY SECURED. |
| | - ADD A NOTE TO COMPLY WITH FLORIDA BUILDING ENERGY |
| | CODE SECTION C 405 MANDATORY LIGHTING CONTROLS. |
| | - FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED |
| | BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE |
| | LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON |
| | OWN CIRCUIT. |
| | - ALL ELECTRICAL BOXES IN DEMISING WALL SHALL COMPLY |
| | WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED |
| | STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE |
| | RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE |
| | SEALING MATERIALS. |
| | - IMPORTANT NOTICE ALL RE ? USED CIRCUITS FOR DIFFERENT |
| | APPLICATIONS SHALL BE RE ? IDENTIFIED IN THE PANEL |
| | BOARD DIRECTORY. NEC 408.4 A |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |