| 2016-08-30 12:10:55 | MECHANICAL PROVISOS | | | 8/30/16 | | | | | | 1) REVISION REQUIRED TO RELOCATE O/A INTAKE FOR AHU-1 | | | FROM THE WALL TO THE ROOF. | | | | | | 2) PROVIDE TIE-DOWN ENGINEERING FOR INSTALLATION OF THE | | | ROOFTOP FANS AND CURBS. | | | | | | 3) SUBMIT A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA | | | FOR THE RUSKIN WALL LOUVERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|