| 2016-07-26 15:42:07 | 2ND REVIEW |
| | |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHOW COMPLIANCE FOR SIDE WALL GRAB BAR. PER FBC ACC |
| | 604.5.1 SIDE WALL. |
| | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) |
| | LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM |
| | THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM |
| | FROM THE REAR WALL. |
| | |
| | 2. MIRROR SHOWS 42IN OF FINISHED FLOOR IT SHALL BE 40IN |
| | MAX . PER FBC ACC 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3. SHOW COMPLIANCE WITH FBC ACC 604.2 LOCATION. |
| | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 |
| | INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM |
| | FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY |
| | ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. |
| | WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR |
| | RIGHT-HAND APPROACH. |
| | |
| | 4. THE TOP OF TOILET SEAT IS SHOWN AS 17IN MAX IT SHALL |
| | SHOW 17IN MIN 19IN MAX. PER FBC ACC 604.4 SEATS. |
| | THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| | |
| | 5. THE TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC |
| | 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 6. THE SERVICE SINK , DRINKING FOUNTAIN AND EYE WASH |
| | STATION SHALL CONNECT TO BUILDING DRAIN DOWNSTREAM OF |
| | THE BATHROOM GROUP. PER FBC PL 912.1 HORIZONTAL WET |
| | VENT PERMITTED. |
| | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| | LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE |
| | VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE |
| | CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND |
| | FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION |
| | OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM |
| | FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH |
| | DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT |
| | INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE |
| | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO |
| | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL |
| | WET VENT. |
| | |