| 2016-07-27 15:18:55 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16040632 |
| | ADD: 3001 OKEECHOBEE BLVD. |
| | CONT: HEDRICK BROTHERS |
| | TEL: 561-689-8880 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. JULY 27/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST FOR WHAT AREA OF WORK IS TO BE COVERED |
| | UNDER THIS PERMIT. THE PLANS DO INDICATE A 3 HOUR FIRE |
| | WALL ON THE PLANS IN ONE AREA AND ONLY A 2 HOUR FIRE |
| | WALL IN ANOTHER AREA. THE SHEET ALS1.1 DO NOT INDICATE |
| | WHAT OCCUPANCIES ARE BEING SEPARATED BY THESE FIRE |
| | WALLS. PLEASE NOTE THAT IN THE 2014 FBC ?B TABLE 706.4 |
| | DOES HAVE THE FOOT NOTE (A) THAT ALLOWS FOR THE |
| | REDUCTION OF 2 HOURS FOR THE OCCUPANCIES COVERED UNDER |
| | THE FOOTNOTE (A) BUT IF THE AREA ON THE OTHER SIDE OF |
| | THE FIREWALL IS A S1 OCCUPANCY MOTOR VEHICLE REPAIR |
| | GARAGE, THEN THERE IS NO REDUCTION IN THE RATING OF THE |
| | FIRE WALL, PLEASE REVIEW THE 2012 IBC-B TABLE 704.5 AND |
| | CODE COMMENTARY. PLEASE PROVIDE A NARRATIVE AS TO THE |
| | AREAS TO BE INCLUDED UNDER THE TYPE VB SPRINKLERED |
| | CONSTRUCTION. |
| | |
| | PLEASE ALSO NOTE IN THE AREA INCREASES TABULATION THE |
| | PLANS INDICATE THIS IS A 2 STORY BUILDING AND TAKING |
| | 300 % ON AREA INCREASES. THE 300% AREA INCREASES CAN |
| | ONLY BE TAKEN ON SINGLE STORY BUILDINGS, FOR |
| | MULTI-STORY BUILDINGS ONLY 200 % INCREASE CAN BE TAKEN |
| | FOR AUTOMATIC FIRE SPRINKLERS. PLEASE REVIEW THE 2012 |
| | IBC-B CODE COMMENTARY FOR SECTION 506.3. PLEASE ALSO |
| | REVIEW THE EQUATION 5-1 AND( AT) IN THE FIRST HALF OF |
| | THE EQUATION. |
| | |
| | 1ST ROUND OF COMMENTS. THE PERMIT APPLICATION ADDRESS |
| | AND PCN NUMBER INDICATES THE WORK IS TO BE COMPLETED AT |
| | THE ADDRESS OF 3001 OKEECHOBEE BLVD. PLEASE DEFINE |
| | WHERE THE NEW ADDITION ROOF LINE ON THE EAST SIDE WILL |
| | END AND THE EXISTING ROOF LINE THE WEST SIDE OF THE OF |
| | THE EXISTING BUILDING TO THE EAST WILL END SHEET A5.0.1 |
| | DETAIL 2.. IT APPEARS THEY WILL BE ADJOINING AND |
| | CREATING ONE LARGE BUILDING PLEASE PROVIDE COMPLIANCE |
| | FOR NEW CONSTRUCTION, 2014 FBC-B TABLE 503, 503.1.2. |
| | BUILDINGS ON THE SAME LOT AND 705.3 BUILDINGS ON THE |
| | SAME LOT. COMPLIANCE WITH 508.3 NON-SEPARATED USE |
| | CANNOT BE CONFIRMED UNTIL THE DISTANCE BETWEEN THE 2 |
| | BUILDINGS CAN BE VERIFIED. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED TO DETERMINE CODE COMPLIANCE. |
| | |
| | 2) 2ND REQUEST. THE SOILS REPORT SUBMITTED IS NOT CLEAR |
| | AS TO THE LOCATION WHERE THE TEST WAS COMPLETED. |
| | THE REPORT PREPARED BY ARDAMAN & ASSOCIATES AAI FILE |
| | NO. 16-1634 INDICATES IT IS FOR THE SCHUMACHER |
| | AUTOGROUP DELRAY LLC THE ADDRESS OF 3031 OKEECHOBEE |
| | BLVD WEST PALM BEACH. UNDER THE HEADING SITE LOCATION |
| | IS INDICATED AS DELRAY BEACH FL. THE SITE VICINITY MAP |
| | FIGURE NO. 1 IS DELRAY BEACH, FL. THE TEST LOCATION |
| | PLAN FIGURE NO. 2 ALSO IS FOR THE DELRAY SCHUMACHER ? |
| | RENOVATION PROJECT, DELRAY BEACH, FLORIDA. IT APPEARS |
| | THIS REPORT IS FOR THE DELRAY BEACH JOBSITE LOCATION. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. / 2014 |
| | FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | |
| | |
| | |
| | 1ST ROUND OF COMMENTS. SHEET S4.1 UNDER THE HEADING OF |
| | FOUNDATION NOTE 1A) THERE WAS A SOILS ENGINEERING |
| | COMPLETED BY ARDAMAN & ASSOCIATES. NO SOILS REPORTS |
| | WERE SUBMITTED, 2 ORIGINAL SIGNED AND SEALED REPORTS |
| | NEED TO BE SUBMITTED FOR COMPLIANCE WITH: |
| | 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) PLEASE PROVIDE COMPLIANCE WITH 2014 FLORIDA BUILDING |
| | CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION: |
| | |
| | BUILDING PROVISO: 106.1 LIVE LOADS POSTED. WHERE THE |
| | LIVE LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A |
| | COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN |
| | DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH DESIGN |
| | LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE OWNER |
| | IN THAT PART OF EACH STORY IN WHICH THEY APPLY, USING |
| | DURABLE SIGNS. IT SHALL BE UNLAWFUL TO REMOVE OR DEFACE |
| | SUCH NOTICES. |
| | |
| | BUILDING PROVISO: 106.2 ISSUANCE OF CERTIFICATE OF |
| | OCCUPANCY. A CERTIFICATE OF OCCUPANCY REQUIRED BY |
| | SECTION 111 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD |
| | SIGNS, REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED. |
| | |
| | BUILDING PROVISO: 106.3 RESTRICTIONS ON LOADING. IT |
| | SHALL BE UNLAWFUL TO PLACE, OR CAUSE OR PERMIT TO BE |
| | PLACED, ON ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE |
| | OR PORTION THEREOF, A LOAD GREATER THAN IS PERMITTED BY |
| | THIS CODE. |
| | |
| | 5) BUILDING PROVISO: SHEET S-2 THE PRE-ENGINEERED |
| | MEZZANINE, STAIRS, HANDRAIL & GUARDRAIL SYSTEMS WILL |
| | NEED THE DESIGN CRITERIA AS LISTED ABOVE IN COMMENT # 3 |
| | AND WILL ALSO NEED TO BE REVIEWED BY THE ENGINEER OF |
| | RECORD FOR CONFORMANCE WITH THEIR OVERALL DESIGN |
| | STRUCTURALLY FOR THIS BUILDING AND FOR LOADING. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. |
| | |
| | 6) BUILDING PROVISO: ROOF TOP FIXED LADDER |
| | |
| | 7)SEMI-COMPLIED. SHEET A1.1.2 SHOWS A LIFT TO THE UPPER |
| | PARTS RACK STORAGE AREA. THE SQUARE FOOTAGE OF 1499 SQ. |
| | FT./ 300= OCCUPANT LOAD OF 5, YOU ALWAYS ROUND UP WE DO |
| | NOT HAVE PARTS OF OCCUPANTS YOU ALWAYS ROUND UP TO THE |
| | NEXT WHOLE NUMBER. PLEASE NOTE SUBMIT THE MANUFACTURERS |
| | SPECS ON THE EQUIPMENT FOR THIS ELEVATOR SYSTEM. 3001.2 |
| | REFERENCED STANDARDS. |
| | EXCEPT AS OTHERWISE PROVIDED FOR IN THIS CODE, THE |
| | DESIGN, CONSTRUCTION, INSTALLATION, ALTERATION, REPAIR |
| | AND MAINTENANCE OF ELEVATORS AND CONVEYING SYSTEMS AND |
| | THEIR COMPONENTS SHALL CONFORM TO ASME A17.1/CSA B44, |
| | ASME A17.3 AND ASME A18.1, ASME A90.1, ASME B20.1, ALI |
| | ALCTV, AND ASCE 24 FOR CONSTRUCTION IN FLOOD HAZARD |
| | AREAS ESTABLISHED IN SECTION 1612.3. THE DIVISION OF |
| | HOTELS AND RESTAURANTS MAY GRANT EXCEPTIONS, VARIANCES |
| | AND WAIVERS TO THE ELEVATOR SAFETY CODE AS AUTHORIZED |
| | BY THE SAFETY CODE FOR ELEVATORS AND ESCALATORS (ASME |
| | A17.1, SECTION 1.2) AND FLORIDA STATUTES (CHAPTER 120.) |
| | |
| | |
| | |
| | 1ST ROUND OF COMMENTS. PLEASE PROVIDE THE SQUARE |
| | FOOTAGE FOR THIS AREA AND THE OCCUPANT LOAD TO SEE IF |
| | THE PLATFORM LIFT HAS TO MEET THE REQUIREMENTS FOR |
| | VERTICAL ACCESSIBILITY 206.7 .3 FOR NEW BUILDINGS. |
| | PLEASE ALSO SUPPLY DOCUMENTATION THAT THE PLATFORM LIFT |
| | SHALL COMPLY WITH ASME A18.1. |
| | |
| | 8) 2ND REQUEST. RESPONSE INDICATES WILL COMPLY. PLEASE |
| | PROVIDE COMPLIANCE WITH 2014 FBC-B 1609.1.2 PROTECTION |
| | OF OPENINGS, 1609.6.4.4.1..COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, ROOF TOP HATCHES. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | NOTE VASD PRESSURES FOUND ON S-4.2 ARE GOOD. IF EITHER |
| | THE CONTRACTOR OR THE DESIGNER OF RECORD PREFER TO HAVE |
| | THE PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS PLEASE |
| | DO SO WITHIN THE WRITTEN NARRATIVE RESPONSE. |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 9) 2ND REQUEST. RESPONSE INDICATES WILL COMPLY. |
| | 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 10) SEMI-COMPLIED. SHEET S-4.1 PROVIDES A GENERIC ROOF |
| | OPENING FRAMING DETAIL. PLANS INDICATE SEE MECHANICAL |
| | PLANS FOR OPENING SIZE. PLEASE SEE DETAIL NOTE (14) # |
| | 12 SMS PER BRACKET EQUALLY SPACED. WHAT THE PLANS DO |
| | NOT INDICATE HOW MANY BRACKETS WILL BE REQUIRED. |
| | SHEET M2.2 NOTE # 3 INDICATES THE ROOF TOP UNIT |
| | GREENHECK SPUN ALUMINUM OUTSIDE AIR INTAKE GRSI-8 INCH, |
| | PLEASE PROVIDE THE ACTUAL OPENING THROUGH THE ROOF FOR |
| | THE ROOF FRAMING SIZE. |
| | 1ST ROUND COMMENTS. THE STRUCTURAL SHEETS DO NOT |
| | PROVIDE ROOF FRAMING DETAILS FOR THE ROOF TOP CURBS |
| | REQUIRED FOR THE ROOFTOP EXHAUST FANS, NOR DOES THE |
| | MECHANICAL PLANS. FOR ALL ROOF TOP EQUIPMENT, CURBS OR |
| | A/C STANDS, DETAILED ATTACHMENT TO THE ROOF FRAMING & |
| | DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE |
| | EQUIPMENT ABOVE. 2014 FBC-B 1604.4 ANALYSIS. LOAD |
| | EFFECTS ON STRUCTURAL MEMBERS AND THEIR CONNECTIONS |
| | SHALL BE DETERMINED BY METHODS OF STRUCTURAL ANALYSIS |
| | THAT TAKE INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, |
| | GEOMETRIC COMPATIBILITY AND BOTH SHORT- AND LONG-TERM |
| | MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED |
| | TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL |
| | FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR |
| | WIND LOADS? |
| | |
| | 11A) SHEET M2.1 KEY NOTE 1 INDICATES THE 2 A/C |
| | CONDENSING UNITS ARE TO BE INSTALLED ON THE ROOF. |
| | SUBMITTED IS A NOA 15-0902.05 REVIEWED BY DUANE MILLAR |
| | FOR KAMM CONSULTING. INDICATES (A) REVIEWED NO |
| | EXCEPTION TAKEN!!!!!! THE STRUCTURAL ENGINEEER OF |
| | RECORD HAS NOT REVIEWED!!!! |
| | PLEASE NOTE: |
| | ** TECHNICAL SHEET 1 THE TYPE OF UNIT IS NOT IDENTIFIED |
| | STANDARD UNIT, HD HEAVY DUTY ASSEMBLY, OR IS THIS A |
| | CUSTOM ASSEMBLY. |
| | ** SHEETS 3-8 HAVE NOT IDENTIFIED SEE STAND EXAMPLE |
| | MECHANICAL UNIT/ STAND CRITERIA/ FACE AREA, NOTE |
| | IDENTIFIED. |
| | ** SHEET 9, 11,12 & 13 SHOW TIE DOWN FRAME ASSEMBLY & |
| | UNIT TIE DOWN. 11, 12 & 13 ARE SPECIFIC TO RHEEM MODEL |
| | NUMBERS!!! NOT IDENTIFIED. |
| | **SHEET 10 IS THE ANCHORING OF THE A/C STAND TO ROOF |
| | FRAMING ASSEMBLY, NOT IDENTIFIED. |
| | |
| | |
| | 11B) COMPLIED. 1013.6 MECHANICAL EQUIPMENT. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |