| 2016-04-15 14:03:31 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16040632 |
| | 4/15/16 |
| | |
| | 1) SUBMIT AC COOLING AN HEATING CALCULATIONS FOR AC- 1 |
| | & AC-2: SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. |
| | 2) SUBMIT ENERGY CALCULATIONS- SECTION C101.4.3 FBC-14 |
| | ENERGY CONSERVATION. |
| | 3) SHEETS M2.1 & M6.1: THE PARTS RECEIVING AND PARTS |
| | DELIVERY AREAS APPEAR TO BE USING AN EXHAUST |
| | VENTILATION SYSTEM TO MEET THE O/A REQUIEMENT LISTED IN |
| | THE O/A SCHEDULE. PROVIDE THE SIZES OF THE O/A INLET |
| | OPENINGS FOR EACH AREA, AND THE SEQUENCE OF OPERATION |
| | FOR THE EXHAUST FANS. PLEASE NOTE IF LOUVERS ARE USED |
| | TO PROTECT THE EXHAUST AND O/A OPENINGS THEY MUST BE |
| | WEATHER RESISTANT PER SECTION 401.5, AND ALSO WIND AND |
| | IMPACT RESISTANT PER SECTION 1609.1.2 FBC-14 BUILDING. |
| | 4) PROVIDE THE CLEARANCE DISTANCE MEASUREMENTS ON THE |
| | PLAN FOR THE AIR INTAKES AND THE EXHAUST OUTLETS- SEE |
| | SECTIONS 401.4 AND 501.3.1 FBC-14 MECHANICAL. |
| | 5) M2.1 & M6.1: PROVIDE A SEQUENCE OF OPERATION FOR THE |
| | EF-2'S IN THE REPAIR GARAGE. |
| | 6) PROVIDE WIND LOAD DESIGN CRITERIA AND ENGINEERED |
| | DETAILS FOR INSTALLATION OF THE ROOFTOP CONDENSERS AND |
| | ROOF RACK, AND THE FANS AND FAN CURBS- SECTION 301.15. |
| | 7) SUBMIT MIAMI-DADE NOA'S OR FLORIDA PRODUCT APPROVALS |
| | FOR THE ROOF RACK, FANS AND CURBS, AND LOUVERS. ALL |
| | SUBMITTALS SHALL BEAR A SHOP DRAWING APPROVAL SIGNATURE |
| | BY THE ENGINEER OF RECORD. |
| | 8) SHEET A8.0.2:=, DETAIL 4: PLEASE INDICATE THE HEIGHT |
| | OF THE PARAPET WALL ABOVE THE FINISHED ROOF LEVEL IN |
| | THE DETAIL- PLEASE NOTE A GUARD RAIL MAY BE REQUIRED |
| | PER SECTION 304.11 FBC-14 MECHANICAL. |
| | 9) INDICATE HOW THE MEZZANINE AREA IS BEING VENTILATED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |