| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - NEC 410.36 B LUMINAIRES SHALL BE SECURELY FASTENED TO |
| | THE FRAMING MEMBER BY MECHANICAL MEANS. SUSPENDED |
| | CEILING SHALL ADEQUATE STRENGTH TO ATTACH LIGHTING OR |
| | THE LUMINAIRES SHALL BE INDEPENDENTLY SECURED. |
| | - ALL ELECTRICAL BOXES IN DEMISING WALL SHALL COMPLY |
| | WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED |
| | STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE |
| | RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE |
| | SEALING MATERIALS. |
| | - NEC 210.8 B8 SERVICE BAYS WHERE ELECTRICAL DIAGNOSTIC |
| | EQUIPMENT, ELECTRICAL HAND TOOLS, OR PORTABLE LIGHTING |
| | EQUIPMENT ARE TO BE USED GFCI PROTECTION IS REQUIRED. |
| | - NEC 300.3 C ON WORK BENCH LAYOUT DETAIL MAKE A NOTE |
| | THAT DIFFERENT RACEWAYS WILL BE USED FOR LOW VOLTAGE |
| | AND POWER CONDUCTORS UNLESS RATED WITH THE SAME |
| | INSULATION. |
| | - NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| | AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| | LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| | WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| | 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING |
| | RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| | ?WR?. |
| | - THE LIGHT ABOVE THE PANELBOARD A SHALL NOT BE |
| | CONTROLLED BY AUTOMATIC MEANS ONLY A MANUAL SWITCH |
| | SHALL SUFFICE. NEC 110.26 D |
| | - NEC 110.26A & 110.24 ARC-FLASH HAZARD WARNING LABEL |
| | AND AVAILABLE FAULT CURRENT MARKING IS MISSING FROM |
| | ELECTRICAL GENERAL NOTES. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |