| Plan Review Notes For Permit 16040630 |
| Permit Number |
16040630 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-13 14:50:10 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 - PROVIDE ON THE PLANS, WHO DREW THE PLANS. IF IT | | | IS AN ENGINEER, THE PLANS MUST HAVE THE ENGINEER STAMP | | | AND SIGNATURE. IF IT IS THE MECHANICAL CONTRACTOR THE | | | PLANS MUST HAVE NAME OF QUALIFIER, NAME OF COMPANY, | | | ADDRESS OF COMPANY AND LICENSE NUMBER. | | | | | | 107.2 - PROVIDE CLEAR AND READABLE PLANS. SHOW ALL DUCT | | | LOCATIONS, DUCT SIZES, CFM QUANTITIES, GRILL SIZES, AHU | | | CLOSET AND CONDENSER LOCATION. PROVIDE CONDENSER TIE | | | DOWN DETAIL AS PER FBC 2014 WIND LOAD REQUIREMENTS. | | | EQUIPMENT INFORMATION (TO INCLUDE BOTH AHU AND | | | CONDENSER - MAKE, MODEL #, TOTAL BTU, KW HEATER SIZE, | | | MAX FUSE SIZE ) |
|