2016-04-13 14:50:10CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 - PROVIDE ON THE PLANS, WHO DREW THE PLANS. IF IT
 IS AN ENGINEER, THE PLANS MUST HAVE THE ENGINEER STAMP
 AND SIGNATURE. IF IT IS THE MECHANICAL CONTRACTOR THE
 PLANS MUST HAVE NAME OF QUALIFIER, NAME OF COMPANY,
 ADDRESS OF COMPANY AND LICENSE NUMBER.
  
 107.2 - PROVIDE CLEAR AND READABLE PLANS. SHOW ALL DUCT
 LOCATIONS, DUCT SIZES, CFM QUANTITIES, GRILL SIZES, AHU
 CLOSET AND CONDENSER LOCATION. PROVIDE CONDENSER TIE
 DOWN DETAIL AS PER FBC 2014 WIND LOAD REQUIREMENTS.
 EQUIPMENT INFORMATION (TO INCLUDE BOTH AHU AND
 CONDENSER - MAKE, MODEL #, TOTAL BTU, KW HEATER SIZE,
 MAX FUSE SIZE )