| 2016-04-19 18:27:25 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. |
| | CODE: FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 1- ENGINEER CALCULATIONS ITEM #1 SHOW 4'X4'X1.5" |
| | INSULATION BOARD FASTENED WITH (12) FASTENERS FOR MAX. |
| | DESIGN PRESSURES OF -82.5PSF. THE FASTENER PATTERN |
| | SHOWN ON ITEM #3 SPECIFIES (6) FASTENERS FOR THE FIELD |
| | AREA, (10) FASTENERS FOR THE PERIMETER AREA AND (16) |
| | FASTENERS FOR THE CORNER AREA. ACCORDING TO SEC. 8.1 OF |
| | RAS 117 THE PRODUCT APPROVAL MAXIMUM DESIGN PRESSURES |
| | SHOWN ON THE SELECTED ASSEMBLY APPLY TO THE FIELD AREA |
| | OF THE ROOF . THEREFORE, THE NUMBER OF FASTENERS CAN |
| | NOT BE REDUCED. ENGINEER NEEDS TO REVISE THE FASTENER |
| | PATTERN TO COMPLY WITH RAS 117 SEC. 8.1. |
| | |
| | 2- ENGINEER PROVIDES NOTE THAT "FASTENER PATTERNS SHALL |
| | BE AS SPECIFIED IN RAS NO. 117, FIG. 2". PROVIDE COPY |
| | OF FIG. 2 FOR CONTRACTOR AND INSPECTOR REFERENCE. NOTE: |
| | FIGURE 2 DOESN'T SHOW FASTENER PATTERN FOR 16 |
| | FASTENERS. ENGINEER TO PROVIDE FIGURE SHOWING PATTERN |
| | TO INSTALL ALL FASTENERS SPECIFIED INCLUDING 16 |
| | FASTENERS AS SPECIFIED TO RESIST THE CALCULATED DESIGN |
| | PRESSURES. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |