Notes
Date Text
2016-05-04 11:26:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLAN TO INCLUDE ROOM DESIGNATIONS, FBC
 1008.1.10. PANIC HARDWARE IS SHOWN ON SOME DOORS BUT
 NOT ALL. NOT ENOUGH INFORMATION PROVIDED TO DEMONSTRATE
 CODE COMPLIANCE.
  
 2. FBC 2014 ACCESSIBILITY 303, THRESHOLD HEIGHT NOT
 CLEAR. IF ADA THRESHOLD OPTION IS APPLICABLE FOR ALL
 DOORS, REVISE PLAN TO INCLUDE THAT INFORMATION (A
 STATEMENT IS SUFFICIENT). IF NOT, REVISE PLAN TO SHOW
 WHICH DOORS WILL COMPLY WITH FBC 2014 ACCESSIBILITY AND
 REVISE PLAN TO SHOW EXEMPTIONS FOR DOORS WHICH WILL NOT
 BE ACCESSIBLE.
  
  