| 2016-05-04 16:17:22 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16040592 |
| | ADD: 1601 FORUM PLACE / 4TH FLOOR CORRIDOR |
| | CONT: FISHER CONSTRUCTION |
| | TEL: 561-691-4716 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. MAY 04/ 2016 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) SHEET ID-2 NOTE TO REMOVE EXISTING CARPET IN |
| | CORRIDOR AND INSTALL NEW CARPET TILES AND ROLL GOODS. |
| | PLEASE PROVIDE DOCUMENTATION THAT THE CARPET FLOOR |
| | FINISHES COMPLIES WITH SECTION 804.4.2 MINIMUM CRITICAL |
| | RADIANT FLUX OR THE EXCEPTION. |
| | |
| | 2014 FBC-B 804.4.2 MINIMUM CRITICAL RADIANT FLUX. |
| | IN ALL OCCUPANCIES, INTERIOR FLOOR FINISH AND FLOOR |
| | COVERING MATERIALS IN ENCLOSURES FOR STAIRWAYS AND |
| | RAMPS, EXIT PASSAGEWAYS, CORRIDORS AND ROOMS OR SPACES |
| | NOT SEPARATED FROM CORRIDORS BY PARTITIONS EXTENDING |
| | FROM THE FLOOR TO THE UNDERSIDE OF THE CEILING SHALL |
| | WITHSTAND A MINIMUM CRITICAL RADIANT FLUX. THE MINIMUM |
| | CRITICAL RADIANT FLUX SHALL NOT BE LESS THAN CLASS I IN |
| | GROUPS I-1, I-2 AND I-3 AND NOT LESS THAN CLASS II IN |
| | GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S. |
| | |
| | EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH |
| | AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE |
| | PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE |
| | REQUIRED, AND MATERIALS COMPLYING WITH DOC FF-1 ?PILL |
| | TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D 2859 ARE |
| | PERMITTED IN ANY AREA WHERE CLASS II MATERIALS ARE |
| | REQUIRED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |