| Plan Review Notes For Permit 16040583 |
| Permit Number |
16040583 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2016-07-08 14:00:57 | 4TH REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16040585 | | | 7/8/16 | | | | | | IN AN EFFORT TO HELP EXPEDITE THE APPROVAL OF THE | | | MECHANICAL PLANS, PLEASE REVIEW THE COMMENTS BELOW AND | | | CONTACT ME AT YOUR EARLIEST CONVENIENCE. | | | | | | 1) REFER TO SECTION 105.3.1.2 WPB AMENDMENTS TO THE | | | FBC: THE SUBMITTED AC CALCULATIONS MUST EITHER BEAR THE | | | SIGNATURE AND SEAL OF THE MECHANICAL ENGINEER OF | | | RECORD, OR BEAR THE SIGNATURE OF THE INSTALLING AC | | | CONTRACTOR. | | | | | | 2) DUCT SMOKE DETECTORS WHERE REQUIRED BY SECTION | | | 606.2.1 SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS. | | | | | | 3) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR | | | INSTALLATION OF THE ROOFTOP CONDENSERS, THE CONDENSER | | | STANDS, AND EXHAUST FANS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|