| Plan Review Notes For Permit 16040576 |
| Permit Number |
16040576 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-21 17:00:20 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO | | | | | | NEC 404.2C SWITCH CONNECTIONS | | | SWITCHES CONTROLLING LIGHTING LOADS SUPPLIED BY A | | | GROUNDED GENERAL PURPOSE BRANCH CIRCUIT, THE GROUNDED | | | CIRCUIT CONDUCTOR FOR THE CONTROLLED LIGHTING CIRCUIT | | | SHALL BE PROVIDED AT THE SWITCH LOCATION. | | | | | | FBC-ER 404.1.1 / 402.4.4 | | | RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT | | | AS WELL AS IC RATED AND SEALED TO NOT COMPROMISE | | | BUILDING THERMAL ENVELOPE. ( 2 CFM ) | | | | | | |
|