| Plan Review Notes For Permit 16040574 |
| Permit Number |
16040574 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-10-20 15:11:16 | 13RD REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: 3RD REQUEST | | | 1) THERE IS A DISCREPANCY ON THE PLAN COVER SHEET IN | | | THE SHEET INDEX. THE FOLLOWING SHEET IS NOT INCLUDED IN | | | THIS SUBMITTAL; | | | LP-1. IS THERE ANY IRRIGATION ON THIS PLAN? CLARIFY AND | | | SUBMIT SHT. LP-1 FOR REVIEW. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 2) THE SANITARY RISER DOES NOT COMPLY WITH 2014 FPC | | | SEC. 912 FOR FIXTURES PERMITTED ON A WET VENT AND THE | | | ALLOWED FIXTURE UNIT LOAD OF THE WET VENT IS EXCEEDED | | | PER TABLE 912.3 OF 2014 FPC. 2ND REQUEST. | | | THE 2ND TOILET IN EACH BATHROOM CAN NOT BE ON THE WET | | | VENT, YOU MIGHT WANT TO CONSIDER USING A CIRCUIT VENT | | | SYSTEM BY CONNECTING THE LAVATORY TO BUILDING DRAIN | | | BETWEEN THE TWO TOILETS. | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. WE CAN SET | | | UP A MEETING TO GET THIS ISSUE RESOLVED. | | | | | | |
|