| 2016-07-20 06:33:43 | 2ND ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | PENDING COMMENTS: |
| | |
| | 9. PROVIDE EXISTING ONE-LINE DIAGRAM AND ALL NEW |
| | SERVICE EQUIPMENT WITH ASSOCIATED WIRE SIZES, CONDUIT |
| | SIZE AND GROUNDING SCHEME. FBC 107.3.5.- PLEASE NOTE |
| | THAT THE NEW SERVICE SHOWN WILL REQUIRE A AIC |
| | CALCULATION NEC 110.9. RISER DIAGRAM SHOWN NOT IN |
| | COMPLIANCE WITH NEC 2011. SERVICE CONDUCTORS AND FEEDER |
| | CONDUCTORS SHOWN FOR 241AMP CALCULATED LOAD AND MAIN |
| | BREAKER 300A IS UNDERSIZED PER NEC 310.15 B 16 TABLE OF |
| | AMPACITIES AND NEC 240.4 OVERCURRENT SELECTION. SHOW |
| | CONDUCTORS AT THE SERVICE DISC TO BE FUSED AND LABEL |
| | SERVICE DISCONNECT TO BE RATED FOR SERVICE ENTRANCE |
| | EQUIPMENT. AN EQUIPMENT GROUNDING CONDUCTOR TO BE |
| | INSTALLED TO PANEL A PER NEC 250.122. CLARIFY #1 |
| | CONDUCTORS SHOWN FROM METER TO PANEL A, NEED TO |
| | COORELATE. |
| | |
| | 1- SHOW ON FLOOR PLAN WHERE THE SERVICE IS LOCATED. |
| | COULD NOT LOCATE PANELBOARD IN HALLWAY AS INDICATED ON |
| | NARRATIVE. PROVIDE NOTES TO INDICATE PROPER SINAGE |
| | REQUIRED AT THE SERVICE, SEE NEC 110.16 ARC FLASH |
| | HAZARD WARNINGS AND NEC 110.24 FIELD MARKING OF |
| | AVAILABLE FAULT CURRENT. SEE VERBIAGE IN CODE SECTION. |
| | NOTES WILL SUFFICE. |
| | |
| | 2- FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE |
| | FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |