| 2016-05-10 14:20:33 | 1) THERE IS A DISCREPANCY ON THE PLAN COVER SHEET IN |
| | THE SHEET INDEX. THE FOLLOWING SHEETS ARE NOT INCLUDED |
| | IN THIS SUBMITTAL; |
| | SP-1, SP-2, LP-1, A-5, A-6. THERE ARE THREE SHEETS |
| | LABELED A-4. CLARIFY. |
| | 2) SHOW THE CLEAR INSIDE SHOWER DIMENSIONS ON THE PLAN. |
| | ( LXW.). COMPLY WITH 2014 FBC-PLUMBING SEC.417.4. |
| | 3) THE MINIMUM WIDTH OF THE ACCESSIBLE TOILET ROOM |
| | SHALL BE 85 INCHES IF BUILT PERFECT. |
| | 4) SHOW THE TYPICAL SIZE (LXW) OF THE WATER CCLOSET |
| | COMPARTMENTS ON THE PLANS. COMPLY WITH 2014 FPC |
| | SEC.405.3.1. |
| | 5) THE DOOR SWINGS INTO THE CLEAR FLOOR SPACE FOR THE |
| | LAVATORY IN THE ACCESSIBLE TOILET ROOM. COMPLY WITH |
| | FBC-ACCESSIBILITY SEC.603.2.3, EXCEPTION #2. |
| | 6) SHTS. A-3, A-4 & P-1 REFER TO THE 2010 FBC. REVISE |
| | THE NOTE TO COMPLY WITH THE 2014 FBC. |
| | 7) WHAT TYPE OF ACTIVITIES WILL BE PERFORMED IN THE |
| | FELLOWSHIP HALL?. WILL THERE BE ANY DAYCARE IN THIS |
| | ADDITION? FBC 107.2.1. |
| | 8) THE SANITARY RISER DOES NOT COMPLY WITH 2014 FPC |
| | SEC. 912 FOR FIXTURES PERMITTED ON A WET VENT AND THE |
| | ALLOWED FIXTURE UNIT LOAD OF THE WET VENT IS EXCEEDED |
| | PER TABLE 912.3 OF 2014 FPC. |
| | 9) THE TWO MOST UPSTREAM WATER CLOSETS IN THE WOMEN'S |
| | RESTROOM ARE NOT PROPERLY VENTED.THE VENT SHALL BE |
| | LOCATED BETWEEN THE TWO WATER CLOSETS. |
| | 10) THE WATER FOUNTAIN IS NOT VENTED. COMPLY WITH 2014 |
| | FPC SEC.901.2, 901.2.1. |
| | 11) THE WATER RISER DIAGRAM SHOWS THE HOT AND COLD |
| | WATER LINES TO ALL THE FIXTURES IN 1/2" PIPE.SUBMIT |
| | VERIFICATION THAT THE THE PRESSURE TO THE FIXTURES AND |
| | THE CAPACITY AT THE FIXTURE OUTLETS WILL COMPLY WITH |
| | 2014 FPC SEC.604.3 & TABLE 604.3. |
| | 12) SHOW THE LOCATION OF THE WATER HEATER ON THE |
| | PLUMBING DRAWING. IF THE WATER HEATER IS PLACED IN A |
| | PAN THEN A PAN DRAIN IS REQUIRED. THE PAN AND DRAIN |
| | SHALL COMPLY WITH 2014 FPC SECS. 504.7, 504.7.1, |
| | 504.7.2. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |