| 2016-04-18 11:14:26 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1. PLEASE DELETE FROM ELECTRICAL NOTES LIST THE |
| | NON-APPLICABLE NOTES FOR RESIDENTIAL DWELLINGS. |
| | 2. PROVIDE A NOTE TO PROVIDE TAMPER RESISTANT |
| | RECEPTACLE TO THE CLASSROOM AREAS AS SHOWN ON DRAWINGS. |
| | NEC 406.14 |
| | 3. CLARIFY GFCI SHOWN IN SHOWER AREA, NEC 406.9C |
| | 4. ADDRESS ALL FIRE DEPARTMENT COMMENTS RELATED TO THE |
| | ELECTRICAL SCOPE. |
| | 5. SHOW ON DRAWINGS THE CIRCUIT DESIGNATION FOR ALL |
| | POWER AND LIGHTING OUTLETS. FBC 107.3.5 |
| | 6. CLARIFY ON DRAWINGS WHAT IS NEW AND WHAT IS |
| | EXISTING, BY DESIGNATING N OR E AS SYMBOLS. |
| | 7. SHOW ON PLANS THE LOCATION OF THE ELECTRICAL SERVICE |
| | AND THE AIR HANDLER EQUIPMENT. |
| | 8. PLEASE CLARIFY THE OCCUPANCY SENSORS SHOWN FOR THE |
| | FAN MOTOR IN CLASSROOM. |
| | 9. PROVIDE EXISTING ONE-LINE DIAGRAM AND ALL NEW |
| | SERVICE EQUIPMENT WITH ASSOCIATED WIRE SIZES, CONDUIT |
| | SIZE AND GROUNDING SCHEME. FBC 107.3.5 |
| | 10. SHOW ON PANEL SCHEDULE THE CIRCUIT IDENTIFICATION |
| | FOR THE AREAS THAT IT WILL SERVE. GENERAL RECEPTACLE |
| | AND LIGHTING DESIGNATION IS NOT CLEAR AND EVIDENT AS |
| | PER NEC 408.4 |
| | 11. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. |
| | PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY |
| | QUESTIONS REGARDING THIS PROJECT. |
| | |