| 2016-05-14 07:47:06 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16040572 |
| | ADD: 641 34TH ST |
| | CONT: HALL ROOFING CONSTRUCTION |
| | TEL: 561-557-5136 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SAT. MAY 14/2016 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) ROOFING ASPHALT SHINGLES 2014 < 4/12 PITCH FBC-R |
| | R905.2.7 UNDERLAYMENT APPLICATION. UNDERLAYMENT SHALL |
| | BE INSTALLED USING ONE OF THE FOLLOWING METHODS: |
| | 1. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (17-PERCENT SLOPE), AND LESS THAN FOUR UNITS |
| | VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| | UNDERLAYMENT SHALL COMPLY WITH ASTM D 226, TYPE I OR |
| | TYPE II OR ASTM D 4869, TYPE II OR TYPE IV OR ASTM D |
| | 6757 AND SHALL BE TWO LAYERS APPLIED IN THE FOLLOWING |
| | MANNER. APPLY A 19-INCH (483 MM) STRIP OF UNDERLAYMENT |
| | FELT PARALLEL TO AND STARTING AT THE EAVES, FASTENED |
| | SUFFICIENTLY TO HOLD IN PLACE. STARTING AT THE EAVE, |
| | APPLY 36-INCH-WIDE SHEETS OF UNDERLAYMENT, OVERLAPPING |
| | SUCCESSIVE SHEETS 19 INCHES (483 MM), AND FASTENED WITH |
| | A 1-INCH (25 MM) ROUND PLASTIC CAP, METAL CAP NAILS OR |
| | NAILS AND TIN-TABS ATTACHED TO A NAILABLE DECK WITH ONE |
| | ROW IN THE FIELD OF THE SHEET WITH A MAXIMUM FASTENER |
| | SPACING OF 12 INCHES (305 MM) O.C., AND ONE ROW AT THE |
| | OVERLAPS FASTENED 6 INCHES O.C. |
| | |
| | 2.AS AN ALTERNATIVE, THE ENTIRE ROOF DECK SHALL BE |
| | COVERED WITH AN APPROVED SELF-ADHERING POLYMER MODIFIED |
| | BITUMEN SHEET MEETING ASTM D 1970 OR AN APPROVED |
| | SELF-ADHERING SYNTHETIC UNDERLAYMENT INSTALLED IN |
| | ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 2) PROVISO: NOTICE: EFFECTIVE APRIL 1/2016 THE |
| | REFERENCED MIAMI-DADE COUNTY ELECTROGALVANIZED |
| | FASTENERS LISTINGS ARE SUSPENDED: |
| | 11--1019.02 & 11-1019.03 BLUELINX CORP. |
| | 12-0423.06 CONTINENAL MATERIALS, INC. |
| | 15-1123.04 PRIME SOURCE BUILDING PRODUCTS, INC. |
| | 13-0530.01 SPECIALTY FASTENING SYSTEM |
| | 12-0423.03 & 12-0423.04 SUMMIT CONGLOMERATE, LLC |
| | 12-1205.11, 12-1205.13 & 13-05 & 13-0514.05 WEATHERPRO, |
| | LLC |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |