| 2016-04-22 10:45:24 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | | PERMIT #16040566 | | | 4/22/16 | | | | | | 1) PLEASE PROVIDE THE LEVEL OF ALTERATION ON THE PLAN- | | | REFER TO SECTION 501.1 FBC-14 EXISTING BUILDING. | | | 2) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND | | | STANDARDS USED IN THE DESIGN OF THE PROJECT. | | | 3) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS | | | ON THE PLAN WITH CORRESPONDING DRAWINGS, DETAILS, AND | | | SPECIFICATIONS. SHOW ALL EXISTING EQUIPMENT AND | | | COMPONENTS TO BE REMOVED, RE-LOCATED, OR REPLACED | | | INCLUDING THE CORRIDORS WHERE IT APPEARS A NEW | | | SUSPENDED CEILING WILL BE INSTALLED. REFER TO SECTIONS | | | 601.2 AND 607 FBC-14 MECHANICAL FOR CODE COMPLIANCE | | | INFORMATION. | | | 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND | | | TABLE 403.3 MECHANCIAL AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS IN ALL ROOMS AND SPACES WHERE MECHANICAL | | | ALTERATIONS ARE PROPOSED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|