2016-04-22 10:45:241ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16040566
 4/22/16
  
 1) PLEASE PROVIDE THE LEVEL OF ALTERATION ON THE PLAN-
 REFER TO SECTION 501.1 FBC-14 EXISTING BUILDING.
 2) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT.
 3) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 ON THE PLAN WITH CORRESPONDING DRAWINGS, DETAILS, AND
 SPECIFICATIONS. SHOW ALL EXISTING EQUIPMENT AND
 COMPONENTS TO BE REMOVED, RE-LOCATED, OR REPLACED
 INCLUDING THE CORRIDORS WHERE IT APPEARS A NEW
 SUSPENDED CEILING WILL BE INSTALLED. REFER TO SECTIONS
 601.2 AND 607 FBC-14 MECHANICAL FOR CODE COMPLIANCE
 INFORMATION.
 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND
 TABLE 403.3 MECHANCIAL AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS IN ALL ROOMS AND SPACES WHERE MECHANICAL
 ALTERATIONS ARE PROPOSED.
  