Plan Review Notes
Plan Review Notes For Permit 16040559
Permit Number 16040559
Review Stop P
Sequence Number 1
Notes
Date Text
2016-04-21 17:42:43PLUMBING COMMENTS:
  
 1.THE FLOOR SINK AND SERVICE SINK ARE NOT VENTED, THE
 VENT ON 6IN BUILDING DOES NOT COMPLY, THE BRANCH DRAIN
 FOR FLOOR SINK AND SERVICE SINK HAS TO BE VENTED
 INDIVIDUALLY VENTED
 SHALL COMPLY WITH FBC PL SEC. 901.2.1
  
 2. SIZE SERVICE SINK DRAIN AND NEW VENT PIPING. PER WPB
 AMEND. SEC. 107.2.1
  
 3.PROVIDE WATER RISER DIAGRAM. PER WPB
 AMEND.107.3.5.13(13)
  
 4. HOT WATER IS REQUIRED FOR ALL FIXTURES FBC PL 607.1
  
 5. INCLUDE LETTER FROM ARCHITECT STATING THAT ALL FOOD
 ITEM ARE PRE PACKED AND NOTHING IS COOKED OR PRE PAIR.
 IF NOT A GREASE INTERCEPTOR WILL BE REQUIRED
 PER WPB AMEND. SEC. 107.2.1
  
 6. PLACE MAILING ADDRESS IN TITLE BLOCK ON EACH SHEET.
 PER WPB AMEND. SEC. 107.2.1
  
 7. PLANS NEED TO BE SIGNED BY ARCHITECT DIGITAL DOES
 NOT COMPLY
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS
 DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A
 COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME,
 THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF
 PLANS.
  
  