| Plan Review Notes For Permit 16040559 |
| Permit Number |
16040559 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-21 17:42:43 | PLUMBING COMMENTS: | | | | | | 1.THE FLOOR SINK AND SERVICE SINK ARE NOT VENTED, THE | | | VENT ON 6IN BUILDING DOES NOT COMPLY, THE BRANCH DRAIN | | | FOR FLOOR SINK AND SERVICE SINK HAS TO BE VENTED | | | INDIVIDUALLY VENTED | | | SHALL COMPLY WITH FBC PL SEC. 901.2.1 | | | | | | 2. SIZE SERVICE SINK DRAIN AND NEW VENT PIPING. PER WPB | | | AMEND. SEC. 107.2.1 | | | | | | 3.PROVIDE WATER RISER DIAGRAM. PER WPB | | | AMEND.107.3.5.13(13) | | | | | | 4. HOT WATER IS REQUIRED FOR ALL FIXTURES FBC PL 607.1 | | | | | | 5. INCLUDE LETTER FROM ARCHITECT STATING THAT ALL FOOD | | | ITEM ARE PRE PACKED AND NOTHING IS COOKED OR PRE PAIR. | | | IF NOT A GREASE INTERCEPTOR WILL BE REQUIRED | | | PER WPB AMEND. SEC. 107.2.1 | | | | | | 6. PLACE MAILING ADDRESS IN TITLE BLOCK ON EACH SHEET. | | | PER WPB AMEND. SEC. 107.2.1 | | | | | | 7. PLANS NEED TO BE SIGNED BY ARCHITECT DIGITAL DOES | | | NOT COMPLY | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS | | | DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A | | | COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME, | | | THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF | | | PLANS. | | | | | | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|