| 2016-04-13 09:06:14 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16040559 | | | 4/13/16 | | | | | | 1) PROVIDE VENTILATION FOR THE UTILITY ROOM PER TABLE | | | 403.3 FBC-14 MECHANICAL. | | | 2) SHEET 2.1: CORRECT THE NOTE IN THE LEGEND INDICATING | | | A KITCHEN EXHAUST FAN: THE FAN SYMBOL IN THE DRAWING IS | | | IN THE TOILET ROOM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|