| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - ALL ELECTRICAL BOXES IN DEMISING WALL SHALL COMPLY |
| | WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED |
| | STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE |
| | RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE |
| | SEALING MATERIALS. |
| | - NEC 300.3 C ON THE SLAB ?? CONDUIT MAKE A NOTE THAT |
| | DIFFERENT RACEWAYS WILL BE USED FOR LOW VOLTAGE AND |
| | POWER CONDUCTORS UNLESS RATED WITH THE SAME INSULATION. |
| | - NEC 110.26A & 110.24 ARC-FLASH HAZARD WARNING LABEL |
| | AND AVAILABLE FAULT CURRENT MARKING IS MISSING FROM |
| | ELECTRICAL GENERAL NOTES. |
| | - FOLLOW UP FIRE COMMENTS IN ADDING EXIT SIGNS AND |
| | EMERGENCY LIGHTING FBC- 1006, 1011 |
| | - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED |
| | BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE |
| | LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON |
| | OWN CIRCUIT. |
| | - NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, PANELBOARDS. |
| | - PROVIDE ON PANEL SCHEDULE THE AIC RATING OF EQUIPMENT |
| | AND AMPERE RATING OF THE BUS BAR. WPBA 107, NEC 110.9 , |
| | 110.10 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |