| 2016-04-13 14:16:44 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 16040513 |
| | W. P. B. PERMIT: 15120060 |
| | ADD: 701 NORTHPOINT # 400 |
| | CONT: KAST CONSTRUCTION |
| | TEL: 561-689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: WED. APRIL 13/ 2016 |
| | ACTION: BUILDING APPROVED |
| | |
| | PLEASE NOTE THE APPROVAL FOR USE OF PROFLEX MAXXIM |
| | SIM-90 IS A ONE TIME APPROVAL. THIS APPROVAL IS NOT FOR |
| | SOUND TRANSFER SINCE THIS IS A OFFICE COMPLEX WITH NO |
| | RESIDENTIAL UNITS. THIS APPROVAL IS FOR THE FLAME |
| | SPREAD INDEX AS REQUIRED BY |
| | 2014 FBC-B 603.1. EXCEPTION 2. INSULATION INSTALLED |
| | BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT |
| | INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| | SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |