| 2016-04-27 19:14:47 | ELECTRICAL REVIEW COMMENTS |
| | |
| | CORRECTIONS REQUIRED: |
| | 1. THERE ARE SEVERAL ITEMS THAT MAY NOT BE TO CODE BUT |
| | WERE INITIALLY MISSED BY BOTH MYSELF AND LATER THE |
| | INSPECTOR. |
| | 2. PROVIDE MANUFACTURER SPECS FOR BOTH, THE RANGE/OVEN |
| | AND HVAC TO CONFIRM THAT THE OCPD AND WIRING AS |
| | INDICATED ON YOUR PANEL SCHEDULES IS ACCEPTABLE, |
| | OTHERWISE CORRECT THE PANEL SCHEDULE AND LOAD CALCS |
| | ACCORDINGLY. |
| | 3. FBC-R303.9 REQUIRE THAT YOU PROVIDE HEAT ENOUGH TO |
| | MAINTAIN 68 DEGREES WITHIN 3? OF THE FLOOR IN EVERY |
| | HABITABLE ROOM. THE HVAC LOADS INDICATED DO NOT REFLECT |
| | THAT. |
| | 4. CORRECTION TO THE SMOKE DETECTOR NOTE. SMOKE |
| | DETECTORS MAY NOT BE WITHIN 20? OF THE RANGE UNLESS IT |
| | CAN BE SILENCED. |
| | 5. IF ROOM 100 IS AN EXTERIOR ROOM IT BECOMES A PORCH |
| | BY CODE STANDARDS AND AS PER NEC 210.52(E)(3), IT |
| | REQUIRES AN OUTLET. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |