| Plan Review Notes For Permit 16040512 |
| Permit Number |
16040512 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-12 07:36:33 | 1ST REVIEW: FBC 2010 RESIDENTIAL, MECHANICAL | | | REVISION PERMIT #16040512 | | | MASTER #15050486 | | | 4/12/16 | | | | | | 1) THE 6" FLEX DUCTS SUPPLYING 240 CFMS EACH TO THE | | | FUTURE BONUS ROOM ARE UNDERSIZED PER ACCA MANUAL D | | | CALCULATIONS. PLEASE INCREASE THE SIZES TO MINIMUIM | | | 10". | | | 2) THE 12" FLEX TRUNK LINE SUPPLYING 600 CFMS TO | | | BEDROOMS 2 & 3 IS UNDERSIZED AND SHOULD INCREASE TO | | | MINIMUM 14" PER ACCA MANUAL D. | | | 3) REVISE THE AIR HANDLER CLOSET DETAIL TO INDICATE THE | | | TOTAL WIDTH OF THE ENCLOSING SPACE SHALL BE MINIMUM 12" | | | WIDER THAN THE AIR HANDLER- SECTION 1305.1.1 FBC-10 | | | RESIDENTIAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|