| Plan Review Notes For Permit 16040459 |
| Permit Number |
16040459 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-11 15:02:24 | ELECTRICAL REVIEW COMMENTS | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 | | | EDITION | | | | | | CORRECTIONS REQUIRED: | | | 1. THIS IS A CLASS I DIVISION I LOCATION AND THEREFORE | | | ALL PROPOSED EQUIPMENT SHALL BE LISTED FOR THE PURPOSE. | | | YOU SHALL PROVIDE SPEC SHEETS FOR THE PROPOSED | | | EQUIPMENT. | | | 2. YOU SHALL SUBMIT A WIRING DIAGRAM INDICATING WHERE | | | YOU INTEND TO PLACE YOUR SEAL-OFFS | | | 3. DESCRIBE CIRCUIT DESIGNATION FOR THE PROPOSED | | | RECEPTACLES. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|