| 2016-10-13 15:50:48 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #16040451 | | | 10/13/16 | | | | | | 1) 2ND REQUEST FOR FIRE DAMPERS FOR DUCT PENETRATING | | | FIRE-RATED CORRIDOR WALLS. PLEASE REFER TO TABLE 1018.1 | | | FBC-14 FOR REQUIRED FIRE-RESISTNCE RATING OF CORRIDORS | | | IN THE R4 OCCUPANCY. PLEASE NOTE THAT PER SECTION | | | 607.5.3 EXCEPTION 1, FIRE DAMPERS CAN BE ELIMINATED IN | | | THE DUCTS IF APPROVED THROUGH-PENETRATION FIRE-STOPPING | | | IS USED TO PROTECT THE ANNULAR SPACE AROUND THE DUCT- | | | SEE SECTION 714.1.1 FBC-14 BUILDING. PLEASE INDICATE | | | ONE MEANS OF PROTECTION OR THE OTHER ON THE PLANS. | | | | | | 2) ONE SET OF PLANS IS MISSING SHEET M0.1 AND THE OTHER | | | IS MISSING M1.1. | | | | | | 3) 2ND REQUEST FOR THE ENERGYGAUGE CALCULATION | | | SUBMITTAL TO BE SIGNED BY THE OWNER. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|