Plan Review Notes
Plan Review Notes For Permit 16040451
Permit Number 16040451
Review Stop P
Sequence Number 2
Notes
Date Text
2016-06-17 16:26:592NDT REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. SHT. A3 FIRST FLOOR REPLACEMENT PIPE TNE NOTE
 DOWNSTREAM OF CLEAN OUT CONNECT EXISTING 2IN PVC AND
 ABOVE IT SAYS CONNECT 4IN PVC IT IS UNCLEAR WHAT YOU
 DOING THERE IF THERE IS A BRANCH LINE THERE SHOW IT ON
 RISER AND PUT NOTE ON IT. PER WPB AMEND.TO FBC SEC.
 107.2.1
  
 2. FIRST FLOOR RISER BATH #5 THE VENT NEEDS TO CONNECT
 TO LAVATORY NOT THE WATER CLOSET. COMPLY WITH FBC RES.
 P3101.1
  
 3. FIRST FLOOR RISER BATH #3 THE VENT NEEDS TO CONNECT
 TO LAVATORY NOT THE WATER CLOSET. COMPLY WITH FBC RES.
 P3101.1
  
 4. SHOW HEIGHT OF HANDICAP LAV. TO COMPLY WITH FBC ACC.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5. SHOW HEIGHT OF TOILET. TO COMPLY WITH FBC ACC.604.4
 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 6. TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 7. MIRROR SHALL COMPLY WITH FBC ACC. 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 8. REAR GRAB BAR SHALL COMPLY WITH FBC ACC 604.5.2 REAR
 WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 9. PROVIDE DIMENSIONS OF ACCESSIBLE SHOWERS AND SHOWER
 VALVES. PER WPB AMEND.TO FBC SEC. 107.2.1
  
 10. SHOW NEW SHOWER ON SECOND FLOW RISER DIAGRAM. PER
 WPB AMEND.TO FBC SEC. 107.2.1
  