Plan Review Notes
Plan Review Notes For Permit 16040451
Permit Number 16040451
Review Stop M
Sequence Number 2
Notes
Date Text
2016-09-09 09:24:522ND REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16040451
 9/9/16
  
 1) FIRE DAMPERS MISSING FOR DUCTS PENETRATING THE RATED
 CORRIDOR/BEDROOM WALLS, AT THE 30/20 RA GRILL AT THE
 MECHANICAL CLOSET, AND AT THE 12/10 RA GRILL AT THE
 BEDROOM/LOUNGE WALL.
  
 2) THE NEW CORRIDOR CANNOT BE USED TO CONVEY RETURN AIR
 VIA THE TRANSFERS FROM THE BEDROOMS- SECTION 601.2.
  
 3) THE PROJECT IS BEING REVIEWED AS A CHANGE OF
 OCCUPANCY PER SECTION 202 FBC-14 EXISTING BUILDING
 CODES. EXISTING CORRIDOR AND OTHER WALLS PREVIOUSLY
 NON-RATED MAY NOW BE REQUIRED TO BE FIRE-RATED (SEE
 BUILDING REVIEW COMMENTS). PLEASE PROVIDE A COMPLETE
 DUCT LAYOUT PLAN SHOWING LOCATIONS OF ALL REQUIRED FIRE
 DAMPERS (NEW OR EXISTING) IN DUCTS PENETRATING
 FIRE-RATED WALLS.
  
 4) PROVIDE DETAILS FOR THE CONTROLS OPERATION AND
 SUPERVISION OF THE RETURN AIR SMOKE DETECTOR AT AHU-1-
 SECTIONS 606.4 AND 606.4.1.
  
 5) PROVIDE FIRE DAMPER INSTALLATION DETAILS.
  
 6) M5.1: PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 COMPLETE DETAILS FOR INSTALLATION OF THE GROUND AND
 WALL-MOUNTED CU'S. SUBMIT A FL. PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE WALL BRACKET.
  
 7) THE OWNER/AGENT MUST SIGN AND DATE THE SUBMITTED
 ENERGY COMPLIANCE FORM R405-2014.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER