| 2016-09-09 09:24:52 | 2ND REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, |
| | ENERGY CONSERVATION CODES |
| | PERMIT #16040451 |
| | 9/9/16 |
| | |
| | 1) FIRE DAMPERS MISSING FOR DUCTS PENETRATING THE RATED |
| | CORRIDOR/BEDROOM WALLS, AT THE 30/20 RA GRILL AT THE |
| | MECHANICAL CLOSET, AND AT THE 12/10 RA GRILL AT THE |
| | BEDROOM/LOUNGE WALL. |
| | |
| | 2) THE NEW CORRIDOR CANNOT BE USED TO CONVEY RETURN AIR |
| | VIA THE TRANSFERS FROM THE BEDROOMS- SECTION 601.2. |
| | |
| | 3) THE PROJECT IS BEING REVIEWED AS A CHANGE OF |
| | OCCUPANCY PER SECTION 202 FBC-14 EXISTING BUILDING |
| | CODES. EXISTING CORRIDOR AND OTHER WALLS PREVIOUSLY |
| | NON-RATED MAY NOW BE REQUIRED TO BE FIRE-RATED (SEE |
| | BUILDING REVIEW COMMENTS). PLEASE PROVIDE A COMPLETE |
| | DUCT LAYOUT PLAN SHOWING LOCATIONS OF ALL REQUIRED FIRE |
| | DAMPERS (NEW OR EXISTING) IN DUCTS PENETRATING |
| | FIRE-RATED WALLS. |
| | |
| | 4) PROVIDE DETAILS FOR THE CONTROLS OPERATION AND |
| | SUPERVISION OF THE RETURN AIR SMOKE DETECTOR AT AHU-1- |
| | SECTIONS 606.4 AND 606.4.1. |
| | |
| | 5) PROVIDE FIRE DAMPER INSTALLATION DETAILS. |
| | |
| | 6) M5.1: PROVIDE THE WIND LOAD DESIGN CRITERIA AND |
| | COMPLETE DETAILS FOR INSTALLATION OF THE GROUND AND |
| | WALL-MOUNTED CU'S. SUBMIT A FL. PRODUCT APPROVAL OR |
| | MIAMI-DADE NOA FOR THE WALL BRACKET. |
| | |
| | 7) THE OWNER/AGENT MUST SIGN AND DATE THE SUBMITTED |
| | ENERGY COMPLIANCE FORM R405-2014. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |