| 2016-06-21 13:41:03 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16040451 |
| | ADD: 2700 BROADWAY |
| | CONT: BEST MASONRY OF S. FL. |
| | TEL: 561-436-3732 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. JUNE 21/2016 |
| | ACTION: DENIED |
| | |
| | NOTICE !!!!!!!! THE SUBMITTED PLANS FOR THE 2ND REVIEW |
| | HAVE NOT BEEN SIGNED NOR SEALED BY THE ENGINEER OF |
| | RECORD. PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS. |
| | EFFECTIVE DATE 05/06/2009 |
| | (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE |
| | SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL |
| | BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL |
| | ENGINEER IN RESPONSIBLE CHARGE. |
| | |
| | 1A-B) COMPLIED. R4 OCCUPANCY. |
| | |
| | 1C)BUILDING PROVISO: THE PROPOSED RESIDENTS ARE CAPABLE |
| | OF SELF-PRESERVATION AND IF IN THE FUTURE RESIDENCE ARE |
| | ADDED THAT ARE NOT CAPABLE OF SELF-PRESERVATION THERE |
| | NEEDS TO BE A PERMIT REQUIRED FOR A CHANGE OF |
| | OCCUPANCY. 2014 FBC-B 310.6. |
| | |
| | 1D) NOTICE: 2014 FBC-B 420.1. OCCUPANCIES IN GROUPS |
| | I-1, R-1, R-2 AND R-3 SHALL COMPLY WITH THE PROVISIONS |
| | OF SECTIONS 420.1 THROUGH 420.5 AND OTHER APPLICABLE |
| | PROVISIONS OF THIS CODE. |
| | |
| | 1E)SEMI-COMPLIED. 420.2 SEPARATION WALLS. WALLS |
| | SEPARATING DWELLING UNITS IN THE SAME BUILDING, WALLS |
| | SEPARATING SLEEPING UNITS IN THE SAME BUILDING AND |
| | WALLS SEPARATING DWELLING OR SLEEPING UNITS FROM OTHER |
| | OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME BUILDING |
| | SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE |
| | WITH SECTION 708 ( FIRE PARTITIONS). THE PLANS DO |
| | INDICATE THE USE OF EXISTING PLASTER AND WOOD LATH AND |
| | THE USE OF 5/8 INCH TYPE X DRYWALL. PLEASE PROVIDE |
| | COMPLIANCE WITH 1 HOUR SEPARATION BETWEEN SLEEPING |
| | ROOMS (420.2) AND A 1 HOUR FIRE RATED CORRIDOR (TABLE |
| | 1018.1 (FOOTNOTE C ALLOWS FOR ? HOUR FIRE RATING WHEN |
| | THE FIRE SPRINKLERS ARE A NFPA 13R, THE PLANS INDICATE |
| | THE SPRINKLER IS A 13D. THE 13 D IS ALLOWED IN THE R-3 |
| | & R-4 RESIDENCE BUT THE FIRE RATING IS STILL 1 HOUR. |
| | |
| | 1F) 2ND REQUEST. 420.3 HORIZONTAL SEPARATION. 2ND FLOOR |
| | BEDROOM #8. FLOOR ASSEMBLIES SEPARATING DWELLING UNITS |
| | IN THE SAME BUILDINGS, FLOOR ASSEMBLIES SEPARATING |
| | SLEEPING UNITS IN THE SAME BUILDING AND FLOOR |
| | ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS FROM |
| | OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME |
| | BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL ASSEMBLIES |
| | IN ACCORDANCE WITH SECTION 711. 2014 FBC-B TABLE |
| | 707.3.10 REQUIRES 2 HOUR FIRE SEPARATION BETWEEN |
| | OCCUPANCIES. |
| | |
| | 1G) [F] 420.4 AUTOMATIC SPRINKLER SYSTEM. GROUP R |
| | OCCUPANCIES SHALL BE EQUIPPED THROUGHOUT WITH AN |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 903.2.8. GROUP I-1 OCCUPANCIES SHALL BE EQUIPPED |
| | THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 903.2.6. QUICK RESPONSE OR |
| | RESIDENTIAL AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.3.2. |
| | |
| | 1H)2ND REQUEST. BEDROOM # 7 SHOWS THE REMOVAL OF A |
| | NON-BEARING WALL, WITH A NOTE TO PROVIDE TEMPORARY |
| | SUPPORT OF EXISTING ROOF SYSTEM WHILE CONDUCTING |
| | STRUCTURAL MODIFICATIONS, IF THE WALL IS NON-BEARING |
| | WHY THE STRUCTURAL SUPPORT REQUIRED? 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1I) NEW COMMENT. THE SLEEPING ROOM # 6 DOES NOT HAVE |
| | EMERGENCY ESCAPE AND RESCUE WINDOWS THAT OPEN DIRECTLY |
| | INTO A PUBLIC WAY, OR TO A YARD OR COURT THAT OPENS TO |
| | A PUBLIC WAY. 2014 FBC-B 1029.1. |
| | |
| | |
| | |
| | 1J) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY |
| | CODE 223.2 HOSPITALS, REHABILITATION FACILITIES, |
| | PSYCHIATRIC FACILITIES AND DETOXIFICATION FACILITIES. |
| | HOSPITALS, REHABILITATION FACILITIES, PSYCHIATRIC |
| | FACILITIES AND DETOXIFICATION FACILITIES SHALL COMPLY |
| | WITH 223.2. |
| | |
| | ACCESS. CODE 223.2.1 FACILITIES NOT SPECIALIZING IN |
| | TREATING CONDITIONS THAT AFFECT MOBILITY. |
| | IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS |
| | THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER |
| | THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE |
| | MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE |
| | PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS |
| | PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY. |
| | |
| | 223.2.2 FACILITIES SPECIALIZING IN TREATING CONDITIONS |
| | THAT AFFECT MOBILITY. |
| | IN FACILITIES SPECIALIZING IN TREATING CONDITIONS THAT |
| | AFFECT MOBILITY, 100 PERCENT OF THE PATIENT SLEEPING |
| | ROOMS SHALL PROVIDE MOBILITY FEATURES COMPLYING WITH |
| | 805. |
| | |
| | ADVISORY 223.2.2 FACILITIES SPECIALIZING IN TREATING |
| | CONDITIONS THAT AFFECT MOBILITY. |
| | CONDITIONS THAT AFFECT MOBILITY INCLUDE CONDITIONS |
| | REQUIRING THE USE OR ASSISTANCE OF A BRACE, CANE, |
| | CRUTCH, PROSTHETIC DEVICE, WHEELCHAIR, OR POWERED |
| | MOBILITY AID; ARTHRITIC, NEUROLOGICAL, OR ORTHOPEDIC |
| | CONDITIONS THAT SEVERELY LIMIT ONE?S ABILITY TO WALK; |
| | RESPIRATORY DISEASES AND OTHER CONDITIONS WHICH MAY |
| | REQUIRE THE USE OF PORTABLE OXYGEN; AND CARDIAC |
| | CONDITIONS THAT IMPOSE SIGNIFICANT FUNCTIONAL |
| | LIMITATIONS. FACILITIES THAT MAY PROVIDE TREATMENT FOR, |
| | BUT THAT DO NOT SPECIALIZE IN TREATMENT OF SUCH |
| | CONDITIONS, SUCH AS GENERAL REHABILITATION HOSPITALS, |
| | ARE NOT SUBJECT TO THIS REQUIREMENT BUT ARE SUBJECT TO |
| | SECTION 223.2.1. |
| | |
| | 1K)(1) COMPLIED. 9805.2 TURNING SPACE. TURNING SPACE |
| | COMPLYING WITH 304 SHALL BE PROVIDED WITHIN THE ROOM. |
| | |
| | 1K)(2) 2ND REQUEST. 805.3 CLEAR FLOOR OR GROUND SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305 SHALL BE |
| | PROVIDED ON EACH SIDE OF THE BED. THE CLEAR FLOOR SPACE |
| | SHALL BE POSITIONED FOR PARALLEL APPROACH TO THE SIDE |
| | OF THE BED. |
| | |
| | 1K)(3) 2ND REQUEST. THE NARRATIVE RESPONSE INDICATES |
| | THE RESTROOMS WERE CODE COMPLIANT WHEN LAST REMODELED. |
| | BOTH OF THE ACCESSIBLE RESTROOMS INDICATE NEW WALL TILE |
| | OM THE WALLS, NEW ACCESSIBLE SHOWER, NEW PLUMBING |
| | FIXTURES. THE PLANS INDICATE THE USE OF GREEN BOARD AS |
| | TILE BACKER BOARD IN THE SHOWERS. |
| | PLEASE REVIEW SECTION 2509.2 BASE FOR TILE. GLASS MAT |
| | WATER-RESISTANT GYPSUM BACKING PANELS, DISCRETE |
| | NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE SHEETS OR |
| | NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS BACKER |
| | UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR C 1325 |
| | AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| | RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| | IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| | SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| | REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| | WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| | |
| | 2509.3 LIMITATIONS. |
| | WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED |
| | IN THE FOLLOWING LOCATIONS: |
| | |
| | 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| | COMPARTMENTS. |
| | |
| | 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| | AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| | |
| | 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| | (305 MM) O.C. FOR 1/2-INCH THICK (12.7 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| | INCHES (406 MM) O.C. FOR 5/8-INCH THICK (15.9 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD. |
| | |
| | |
| | 805.4 TOILET AND BATHING ROOMS. TOILET AND BATHING |
| | ROOMS THAT ARE PROVIDED AS PART OF A PATIENT OR |
| | RESIDENT SLEEPING ROOM SHALL COMPLY WITH 603. WHERE |
| | PROVIDED, NO FEWER THAN ONE WATER CLOSET, ONE LAVATORY, |
| | AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH THE |
| | APPLICABLE REQUIREMENTS OF 603 THROUGH 610. |
| | |
| | 1L) 2ND REQUEST. PLEASE SHOW HOW COMPLIANCE WITH |
| | 202.4.1 DISPROPORTIONATE COST WILL BE MET. THE VALUE OF |
| | THE JOB AS INDICATED, $145,000.00 X .20%= $29,000.00 |
| | DOLLARS ARE TO BE SPENT IN ACCESSIBLE UPGRADES AND IN |
| | THIS ORDER: |
| | 2014 FBC-ACCESS. CODE. 202.4.1 DISPROPORTIONATE COST. |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | PLEASE PROVIDE AN ITEMIZED LIST IN THE ORDER LISTED |
| | ABOVE OF WHERE THE FUNDS WILL BE SPENT IN MAKING |
| | ACCESSIBLE UPGRADES. PLEASE HAVE THE ACCESSIBLE UPGRADE |
| | LIST ON EITHER THE CONTRACTORS OR THE DESIGNER OF |
| | RECORD LETTERHEAD TAKING OWNERSHIP OF THE DOCUMENT. |
| | |
| | 1M) SHEET A1: PROVISO: NOTE ALL EXTERIOR WINDOW & DOORS |
| | ARE UNDER A SEPARATE PERMIT. |
| | |
| | 2) THE COVERSHEET ALSO LIST THE BUILDING TYPE AS A |
| | BUILDING TYPE V THE PLANS DO NOT INDICATE IF THE |
| | BUILDING IS A TYPE VA OR VB. CLASSIFY BUILDING TYPE AS |
| | TO 2014 FBC-B TABLE 503 & TABLE 601. |
| | |
| | 3)2ND REQUEST. THE COVERSHEET INDICATES THIS STRUCTURE |
| | IS FIRE SPRINKLERED BUT DOES NOT INDICATE AS TO WHAT |
| | TYPE OF SYSTEM IS INSTALLED IN THIS STRUCTURE NOR IS |
| | THERE AN EXISTING FIRE SPRINKLER PLAN LAYOUT OR |
| | PROPOSED CHANGES TO THE EXISTING FIRE SPRINKLER PLAN. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS: |
| | (5) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | EARLY WARNING SMOKE EVACUATION SYSTEMS |
| | SCHEMATIC FLOOR PLAN FOR FIRE SPRINKLERS |
| | |
| | 4) 2ND REQUEST. THE RESPONSE IS IN THE NARRATIVE BUT |
| | NOT INDICATED IN THE PLANS, ADD THE ALTERATION LEVEL TO |
| | THE PLANS. THE DESIGNER OF RECORD HAS NOT INDICATED TO |
| | WHAT CODE THE PLANS WERE DESIGNED TOO? 2014 FBC/ 5TH |
| | EDITION WAS ADOPTED STATE WIDE ON JUNE 30/ 2015. PLEASE |
| | NOTE THE DESIGNER OF RECORD HAS NOT INDICATED TO WHICH |
| | METHOD OF COMPLIANCE WAS CHOSEN FOR CODE COMPLIANCE |
| | UNDER THE 2014 FBC-EXISTING BUILDING CODE? 2014 |
| | FBC-EXISTING BUILDING CODE 301.1. THE REPAIR, |
| | ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR RELOCATION |
| | OF ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE |
| | METHODS LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS |
| | SELECTED BY THE APPLICANT. |
| | |
| | 5) 2ND REQUEST. SHEET A1 INDICATES THE FRONT ENTRY |
| | STEPS THE REMOVAL OF AN EXISTING STEEL PIPE HANDRAIL |
| | AND REPLACEMENT WITH A NEW WROUGHT IRON HANDRAIL PER |
| | THE REQUIREMENTS OF THE 2014 FBC. PLEASE NOTE THE |
| | DESIGNER OF RECORD WILL NEED TO PROVIDE THE DESIGN FOR |
| | THE HANDRAIL AND NOT JUST QUOTE CODE COMPLIANCE TO BE |
| | ACHIEVED. |
| | |
| | SHEET A1 SHOWS A SECTION THROUGH THE FRONT STAIRS, |
| | SECTION B, IT DOES NOT INDICATE WHERE THIS SECTION B. |
| | SHEET A2 DOES SHOW A ENTRY STAIR AND HAND RAIL. PLEASE |
| | NOTE THIS SECTION IS SO OLD IT REFERENCES 100 PSF LIVE |
| | LOAD, PER SBCCI CHAPTER 16. PLEASE UPDATE THE CODE TO |
| | THE 2014 FBC-B. |
| | |
| | THIS SAME SECTION SHOWS A HANDRAIL SYSTEM PLEASE SHOW |
| | COMPLIANCE WITH 2014 FBC-B 1012.6 HANDRAIL EXTENSIONS. |
| | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING |
| | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| | ADJACENT STAIR FLIGHT OR RAMP RUN. WHERE HANDRAILS ARE |
| | NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| | EXTEND HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND |
| | THE TOP RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF |
| | ONE TREAD BEYOND THE BOTTOM RISER. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE |
| | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR SHALL THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION? |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |