Plan Review Notes
Plan Review Notes For Permit 16040451
Permit Number 16040451
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-21 11:13:22JOB PERMIT NUMBER: 16040451
 JOB ADDRESS: 2700 BROADWAY
 WEST PALM BEACH 33407
 DATE: APRIL 21 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - DEFINE ALTERATION LEVEL EITHER 1 , 2 OR 3 THEN IN
 DETAIL DESCRIBE THE EXTENT OF THE SCOPE OF WORK WBPA
 107
 - WBPA- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT.
 - NEC 517 ALL PATIENT CARE BED AREAS MUST HAVE AN
 ISOLATED EQUIPMENT GROUNDING CONDUCTOR FOR ALL
 RECEPTACLES AND LIGHTING WITHIN 7 ?? FEET FROM FLOOR
 GRADE. WIRING METHODS MUST BE EMT , HOSPITAL GRADE MC
 OR AC CABLE WITH GREEN EXTERIOR METAL CLAD , THEREFORE
 NM CABLE ( PROPER TERMINOLOGY FOR ROMEX WHICH IS A
 BRAND NAME. ) ISN?T ACCEPTABLE IN PATIENT AREAS.
 FURTHERMORE TAMPER RESISTANT RECEPTACLES SHALL BE
 INSTALLED IN OTHER AREAS NOT CLASSIFIED AS CARE AREA.
 - FBC- 450 NURSING HOMES SHALL HAVE THE FOLLOWING
 ESSENTIAL ELECTRICAL SYSTEMS, FIRST A EMERGENCY SYSTEM
 WITH CRITICAL BRANCH CIRCUITS VIA A GENERATOR OR OTHER
 POWER SOURCE, SECOND A LIGHTNING PROTECTION SYSTEM WITH
 EQUIPOTENTIAL BONDING TO THE BUILDING GROUND, THIRD AND
 LAST A SURGE PROTECTION SYSTEM AT THE SERVICE EQUIPMENT
 AND PANEL BOARDS.
 - A SMOKE DETECTOR IS MISSING IN FRONT OF THE FIRE
 ALARM PANEL IN THE NEW PANTRY ROOM PER NFPA 72. NEC 760
 THE FIRE ALARM CIRCUIT SHALL BE A 20 AMP DEDICATED
 CIRCUIT IDENTIFIED WITH RED MARKING IN PANEL BOARD
 IDENTIFICATION LABELING. ( MECHANICAL PROTECTION
 REQUIRED. )
 - FBC- 450 A READING NIGHT LAMP SHALL BE PROVIDED IN
 ALL BEDROOMS WITH A SWITCH ACCESSIBLE NEARBY THE LIGHT.
 PANELS LOCATED IN SPACES SUBJECT TO STORAGE SHALL BE
 MARKED ? ELECTRICAL ? NOT FOR STORAGE?. ( PROPER
 WORKING CLEARANCE MUST BE MAINTAINED AT ALL TIMES. )
 - SECOND FLOOR HAS A EXTERIOR DOOR NOT LEADING TO A
 BALCONY OR MEANS OF EGRESS STAIRWAY PLEASE CLARIFY ?
 ALL EXTERIOR LIGHTING MUST HAVE A MINIMUM OF 1 FT
 CANDLE ILLUMINATION FOR MEANS OF EGRESS UNTIL PUBLIC
 WAY IS SAFELY REACHED.
 - NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 - NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE
 DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910
 MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS.
 RELOCATE THE UNITS ACCORDINGLY.
 - THE CURRENT APPLICABLE CODES ARE: FLORIDA FIRE
 PREVENTION CODE: 2012, NFPA 1: 2012, NFPA 70, (NEC):
 2011, NFPA 72: 2010, NFPA 101: 2012, FBC- 5TH EDITION:
 2014.
 -
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER