| 2016-05-02 11:15:42 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | THE FOLLOWING COMMENTS WILL BE ISSUED AS A PROVISO WITH | | | THE INTENT OF THE REVISION SUBMITTAL TO ADD THE STATED | | | BELOW CORRECTIONS. | | | | | | | | | - FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. | | | - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT, | | | SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET | | | SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE | | | SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE | | | LOCATED WITHIN 25 FT. OF THE EQUIPMENT. | | | - ON NEW BATH DOUBLE SINK PROVIDE A SECOND GFCI TO | | | COMPLY WITH AN OUTLET WITHIN 3 FT OF THE OUTSIDE EDGE | | | OF EACH BASIN NEC 210.52 D | | | - IN THE ATTIC ENTRANCE PROVIDE A LIGHTING OUTLET | | | NEARBY AHU # 2 FOR SERVICING PURPOSES NEC 210.70 A 3 |
|